5587001-YSG-A-520 | Start-Up & Operation Guide
82
Table 26: Menus and Submenus (Continued)
Menu
Submenu
Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Details
(
Htg > Service
> Stage 1–
Stage 8
HeatFaults (Applicable to Staged Gas
Heat)
Not Installed, Unexpected Flame Main Burner,
Unexpected Flame Split Manifold Burner,
Unexpected Flame On Both Burners, Air Pressure
Low Closed with Inducer Off, Air Pressure High
Closed with Inducer Off, Air Pressure Low Open -
Should Be Closed, Air Pressure High Switch State
Mismatch, Fuse Is Open, Primary Limit Open, Main
Burner Exceeds Max Ignition Tries, Split Burner
Exceeds Max Ignition Tries, Both Burners Exceed
Max Ignition Tries, Main Burner Exceeds Flame
Loss Count, Split Burner Exceeds Flame Loss
Count, Both Burners Exceed Flame Loss Count,
Main Gas Valve Shorted To 24VAC, Split Burner
Gas Valve Shorted To 24VAC, Both Gas Valves
Shorted To 24VAC, Main Valve Staging Failure,
Split Manifold Gas Valve Staging Failure, Both Gas
Valves Staging Failure, Invalid ID Plug Installed,
Board Failure, No Alarm, Unknown Fault
HeatFaults (Applicable to Modulating
Gas Heat)
Not Installed, Board Failure, Failed Ignition,
Primary Limit Failure, Modulation Valve Failure,
Air Pressure Sensor Reading Low, Air Pressure
Sensor Reading High, Unexpected Flame Main
Burner, No Enable Signal During Call for Heat,
Open Fuse, Unexpected Flame Split Manifold
Burner, Invalid ID Plug Installed, No Alarm,
Unknown Fault
H1 (Heating Stage Command 1)
OFF, ON
H1OnTmr (Heating Stage 1 Minute On
Time Remaining)
seconds
H1ASCDTmr (Anti-Short Cycle Delay
Time Remaining H1)
seconds
H1-Runtime (Heating Stage 1
Accumulated Runtime)
hours (0–10,000)
H1-Starts
counts (0–2,000,000)
H1-Cap (Heating Capacity 1)
(0-10,000)
ModHtgOut (Modulating Heat Output,
Applicable only to Stage -1)
% (0–100)
Htg > Safeties Water FS (Low Temperature Water Coil
Freezestat)
Normal, Alarm
Htg > Prop
OprZT (Operational Zone Temperature)
deg F
DAT (Discharge Air Temperature)
deg F
W1 - Thermostat
OFF, ON
W2 - Thermostat
OFF, ON
HWV (Hydronic Heat Valve % Command) %
HydReverse (Hydronic Heat Valve
Reverse Acting) / No
No, Yes
Freeze-Sp (Freeze Condition Setpoint)
deg F (20–32)
SF > Setup
FanOnOcc (Continuous Ventilation) / Yes
Yes, No
FanOffDlyHeat (Fan Off Delay for Heat)
/ 0 seconds)
seconds (0–30)