5587001-YSG-A-520 | Start-Up & Operation Guide
32
Table 14: Condenser Boards Field Terminal Points
Callout
Description
1-bit Position
2-bit Position
Pin
1
Condenser Board 1 DIP Switch
OFF
OFF
S4
Condenser Board 2 DIP Switch
ON
ON
NOTE:
There are two condenser boards installed. On the control board panel, condenser board 1 is above board 2.
1
LD27998
Figure 6: Condenser Boards
Table 15: Options Board Field Terminal Points
Callout
Name
Description
IO Type
IO Number
Pin
1
DAP-SP
Discharge Air Static Pressure Setpoint
AI
7
W25
2
DAT-SP
Discharge Air Temperature Setpoint
AI
8
W21
1
2
LD27996
Figure 7: Options Board