YORK
5587001-YSG-A-520 | Start-Up & Operation Guide
114
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
CF-1A
MV
29935
R
CF-1A
Condenser Fan
1A
Displays the command of condenser
fan CF-1A 0 = OFF 1 = ON
CF-1B
MV
29936
R
CF-1B
Condenser Fan
1B
Displays the command of condenser
fan CF-1B 0 = OFF 1 = ON
CF-2A
MV
29937
R
CF-2A
Condenser Fan
2A
Displays the command of condenser
fan CF-2A 0 = OFF 1 = ON
CF-2B
MV
29938
R
CF-2B
Condenser Fan
2B
Displays the command of condenser
fan CF-2B 0 = OFF 1 = ON
C2B
MV
29939
R
C2B
Compressor 2B
Command
Displays the command of
compressor C2B 0 = OFF 1 = ON
C2B-En
MV
29946 R/W
C2B-En
Compressor 2B
Enabled
A BAS command to enable
compressor 2B 0 = NO 1 = YES
C2B-S
MV
29949
R
C2B-S
Compressor 2B
Status
Displays the unit compressor 2B
status
0 = OFF/idle
1 = ON/minimum ON time
2 = ON/normal command
3 = OFF/cooling is disabled
Coast-En
MV
29965 R/W
Coast-En
Coast Enable
A BAS command for unit to enter
coast mode 0 = disable 1 = enable
DAT-SPconfig
MV
29968 R/W
DAT-SPconfig
DAT Setpoint
Configuration
A BAS command to select DAT
schedule
0 = fixed
1 = OAT reset
2 = supply fan reset
3 = ZT reset
4 = external mode
DownInOccAlm
MV
29969
R
DownInOccAlm
Unit Down in
OCC Alarm
Displays the unit in occupied alarm
status 0 = normal 1 = alarm
H4
MV
29976
R
H4
Heating Stage
Command 4
Displays the command of heating
stage 4 0 = OFF 1 = ON
H4-S
MV
29978
R
H4-S
Heating Stage 4
Status
Displays the status of heating stage 4
0 = OFF/idle
1 = ON/minimum ON time
2 = ON/normal command
3 = OFF/heating is disabled
H5
MV
29980
R
H5
Heating Stage
Command 5
Displays the command of heating
stage 5 0 = OFF 1 = ON
H5-S
MV
29982
R
H5-S
Heating Stage 5
Status
Displays the status of heating stage 5
0 = OFF/idle
1 = ON/minimum runtime timer
2 = ON/normal command
3 = OFF/heating is disabled
H6
MV
29984
R
H6
Heating Stage
Command 6
Displays the command of heating
stage 6 0 = OFF 1 = ON
H6-S
MV
29986
R
H6-S
Heating Stage 6
Status
Displays the status of heating stage 6
0 = OFF/idle
1 = ON/minimum runtime timer
2 = ON/normal command
3 = OFF/heating is disabled
Table 32: BACnet Points List (Continued)