YORK
5587001-YSG-A-520 | Start-Up & Operation Guide
108
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
OprOcc
MV
29517
R
OprOcc
Operational
Occupancy
Displays the occupancy status of the
unit
0 = OCC
1 = UNOCC
2 = bypass
3 = standby
OccMode
MV
29518 R/W
OccMode
Occupancy Mode
A BAS command that allows the unit
to be placed in a occupancy mode
0 = schedule 1 = external
NetTempOcc
MV
29519 R/W
NetTempOcc
Network
Temporary
Occupancy
Request
A BAS command to request network
temporary occupancy
0 = false 1 = true
NetOcc
MV
29520 R/W
NetOcc
Network
Occupancy
Request
A BAS command to request network
occupancy
0 = OCC
1 = UNOCC
2 = not set
ZTSrc
MV
29523
R
ZTSrc
ZT Source
Displays the source of ZT input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
IAQSrc
MV
29528
R
IAQSrc
IAQ Source
Displays the source of IAQ (CO
2
)
input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
SHSrc
MV
29532
R
SHSrc
Space Humidity
Source
Displays the source of
space humidity input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
OprFanReq
MV
29534
R
OprFanReq
Operating Fan
Request
Displays the status of supply fan
request 0 = OFF 1 = ON
FanReqSrc
MV
29535
R
FanReqSrc
Fan Request
Source
Displays the source of supply fan
request input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority"
NetFanReq
MV
29536 R/W
NetFanReq
Network Override
Fan Request
A BAS command that allows user to
request for supply fan
0 = OFF 1 = ON
OATSrc
MV
29542
R
OATSrc
OAT Source
Displays the source of OAT input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
Table 32: BACnet Points List (Continued)