YORK
Start-Up & Operation Guide | 5587001-YSG-A-520
105
Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
H5-Starts
AV
29983
R
H5-Starts
Heating Number
Times ON 5
Displays the heating start counts for
stage 5
H6-Runtime
AV
29985
R
H6-Runtime
Heating Stage
6 Accumulated
Runtime
Displays the total runtime for stage 6
heating (hours)
H6-Starts
AV
29987
R
H6-Starts
Heating Number
Times ON 6
Displays the heating start counts for
stage 6
H7-Runtime
AV
29989
R
H7-Runtime
Heating Stage
7 Accumulated
Runtime
Displays the total runtime for stage 7
heating (hours)
H7-Starts
AV
29991
R
H7-Starts
Heating Number
Times ON 7
Displays the heating start counts for
stage 7
H8-Runtime
AV
29993
R
H8-Runtime
Heating Stage
8 Accumulated
Runtime
Displays the total runtime for stage 8
heating (hours)
HE-T
AV
30004
R
HE-T
Heat Entering
Temperature
Displays the active heat entering
temperature (°F)
HighSpeedFan-
MinPos
AV
30006 R/W
HighSpeedFan-
MinPos
Economizer
Damper Minimum
Position High
Speed Fan
A BAS command to adjust outside
air damper minimum position for high
speed fan (0–100%)
HRW-O
AV
30008
R
HRW-O
Heat Recovery
Wheel Output
Displays the ERW control output (%)
HtgCapLim
AV
30010 R/W
HtgCapLim
Heating Capacity
Limit
A BAS command to adjust the
heating capacity limit (0–100%)
HtgDATLo-SP
AV
30011 R/W
HtgDATLo-SP
Heating DAT
Lower Setpoint
A BAS command to adjust heating
DAT lower setpoint (85.0–134.0°F)
HtgDATUp-SP
AV
30012 R/W
HtgDATUp-SP
Heating DAT
Upper Setpoint
A BAS command to adjust heating
DAT upper setpoint (85.0–134.0°F)
Hum-SP
AV
30014 R/W
Hum-SP
Humidification
Setpoint
A BAS command to adjust
humidification setpoint (0–100 %RH)
ModCompOut
AV
30017
R
ModCompOut
Modulating
Compressor
Output
Displays the active modulating
compressor value (0–100%)
ModCondFan1Out
AV
30018
R
ModCondFan1Out
Modulating
Condenser Fan 1
Output
Displays the active modulating
condenser fan 1 value (0–100%)
ModCondFan2Out
AV
30019
R
ModCondFan2Out
Modulating
Condenser Fan 2
Output
Displays the active modulating
condenser fan 2 value (0–100%)
ModHtgOut
AV
30020
R
ModHtgOut
Modulating Heat
Output
Displays the active modulating heat
value (0–100%)
OprHtgDAT-SP
AV
30021
R
OprHtgDAT-SP
Operating Heating
DAT Setpoint
Displays the active heating DAT
setpoint (°F)
PFILT-DP
AV
30022
R
PFILT-DP
Pre-Filter
Differential
Pressure
Displays the differential pressure for
first filters (pre-evap) (iwg)
RAD-O
AV
30025
R
RAD-O
Return Air
Damper
Command
Displays the status of return air
damper command (%)
Table 32: BACnet Points List (Continued)