YORK
Start-Up & Operation Guide | 5587001-YSG-A-520
117
Operation
Faults
Table 33: Faults List
Fault Type
Description
Caused By
Critical
Circuit 1 locked out due to safety chain
One of the safety chain switches has
opened three times
Critical
Circuit 2 locked out due to safety chain
One of the safety chain switches has
opened three times
Critical
Circuit 1 locked out due to low pressure
Low pressure switch tripped three times
Critical
Circuit 2 locked out due to low pressure
Low pressure switch tripped three times
Critical
C1A locked out due to high pressure
HP switch has tripped three times
Critical
C1B locked out due to high pressure
HP switch has tripped three times
Critical
C1C locked out due to high pressure
HP switch has tripped three times
Critical
C2A locked out due to high pressure
HP switch has tripped three times
Critical
C2B locked out due to high pressure
HP switch has tripped three times
Critical
C2C locked out due to high pressure
HP switch has tripped three times
Critical
C1A locked out due to low pressure
LP switch has tripped three times
Critical
C1B locked out due to low pressure
LP switch has tripped three times
Critical
C1C locked out due to low pressure
LP switch has tripped three times
Critical
C2A locked out due to low pressure
LP switch has tripped three times
Critical
C2B locked out due to low pressure
LP switch has tripped three times
Critical
C2C locked out due to low pressure
LP switch has tripped three times
Critical
Unit shutdown due to smoke, etc.
A device in the shut down circuit has
opened
Critical
Exhaust/return fan VFD failure
Abnormal condition exists on the exhaust/
return fan VFD
Critical
Supply fan VFD 1 failure
Abnormal condition exists on the supply
fan 1 VFD
Critical
Supply fan VFD 2 failure
Abnormal condition exists on the supply
fan 2 VFD
Critical
No heat/cool due to unreliable space temperature There is no reliable space temperature
reference
Critical
Option communication failure
Loss of communication to options board.
Check SA bus wiring and connections
Critical
Building system interface board communication
failure
Loss of communication to building system
interface board. Check SA bus wiring and
connections
Critical
Condenser 1 communication failure
Loss of communication to refrigeration
1 board. Check SA bus wiring and
connections
Critical
Condenser 2 communication failure
Loss of communication to refrigeration
2 board. Check SA bus wiring and
connections
Critical
Outputs disabled due to low input V
Loss of 24 VAC power to 24 VAC
OUTPUT terminal
Critical
Outputs limited due to brownout input V
Low voltage on 24 VAC OUTPUT terminal
Critical
Cooling locked out - condensate overflow
Condensate drain is clogged
Critical
Unit locked out due to high duct static pressure
Duct static pressure has exceeded
setpoint