YORK
Start-Up & Operation Guide | 5587001-YSG-A-520
111
Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
H3
MV
29734
R
H3
Heating Stage
Command 3
Displays the command of heating
stage 3 0 = OFF 1 = ON
H1-S
MV
29735
R
H1-S
Heating Stage 1
Status
Displays the status of heating stage 1
0 = OFF/idle
1 = ON/minimum runtime timer
2 = ON/normal command
3 = OFF/heating is disabled
H2-S
MV
29736
R
H2-S
Heating Stage 2
Status
Displays the status of heating stage 2
0 = OFF/idle
1 = ON/minimum runtime timer
2 = ON/normal command
3 = OFF/heating is disabled
H3-S
MV
29737
R
H3-S
Heating Stage 3
Status
Displays the status of heating stage 3
0 = OFF/idle
1 = ON/minimum runtime timer
2 = ON/normal command
3 = OFF/heating is disabled
HydReverse
MV
29742 R/W
HydReverse
Hydronic Heat
Valve Reverse
Acting
A BAS command to enable reverse
acting hydronic heat valve
0 = NO 1 = YES
DATTemper-En
MV
29745 R/W
DATTemper-En
DAT Tempering
Enable
A BAS command to enable discharge
air tempering 0 = NO 1 = YES
Econ-En
MV
29747 R/W
Econ-En
Economizer
Enabled For
Operation
A BAS command to enable
economizer
0 = NO 1 = YES
Econ-Free
MV
29749
R
Econ-Free
Economizer Free
Cooling Available
Displays the availability of free
cooling through economizer
0 = NO 1 = YES
Econ-S
MV
29750
R
Econ-S
Economizer
Status
Displays the status of economizer
0 = disabled
1 = damper not functional
2 = purge
3 = unavailable sensor fault
FreeClg-Mode
MV
29751
R
FreeClg-Mode
Free Cooling
Current Mode
Displays the status of the active
economizer mode:
0 = dry bulb temperature
1 = differential dry bulb temperature
2 = single enthalpy
3 = dual enthalpy
4 = unreliable
FreeClg-Sel
MV
29752 R/W
FreeClg-Sel
Free Cooling
Selection
Allows for the selection of the
economizer mode to use:
0 = dry bulb temperature
1 = differential dry bulb temperature
2 = single enthalpy
3 = dual enthalpy
4 = unreliable
DVent-Mode
MV
29765 R/W
DVent-Mode
Demand
Ventilation Mode
of Operation
A BAS command to enable demand
ventilation mode
0 = disabled
1 = controlled by IAQ
2 = difference between IAQ and OAQ
Table 32: BACnet Points List (Continued)