Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
SatSucTemp2
AV
30055
R
SatSucTemp2
Saturated Suction
Temperature 2
Displays the active system 2 saturated
suction line temperature (°F)
H8-Starts
AV
30056
R
H8-Starts
Heating Number
Times ON 8
Displays the heating start counts for
stage 8
DehumEvapLowSp
AV
30061 R/W DehumEvapLowSp Dehum Evap Low
Setpoint
A BAS command to adjust
dehumidification evaporator low
setpoint (40°F)
Name
CSV 29804 R/W
Name
Unit Name
Displays the unit name
Serial#
CSV 29806 R/W
Serial#
Unit Serial
Number
Displays the unit serial number
FirmVer
CSV 29807
R
FirmVer
Firmware Version
Displays the firmware version
DevName
CSV 29818 R/W
DevName
Device Name
A BAS command to input device name
Htg-Type
MV
29501 R/W
Htg-Type
Heating Control
Type
A BAS command to select the current
operating mode:
0 = none
1 = gas
2 = electric
3 = hot water
4 = steam
ExFType
MV
29503 R/W
ExFType
Exhaust Type
A BAS command to select the current
operating mode:
0 = none
1 = barometric
2 = modulating damper
3 = VFD
Y1-Tstat
MV
29504
R
Y1 - Thermostat
Y1 - Thermostat
Displays the thermostat call for stage
1 cooling 0 = OFF 1 = ON
Y2-Tstat
MV
29505
R
Y2 - Thermostat
Y2 - Thermostat
Displays the thermostat call for stage
2 cooling 0 = OFF 1 = ON
W1-Tstat
MV
29508
R
W1 - Thermostat
W1 - Thermostat Displays the thermostat call for stage
1 heating 0 = OFF 1 = ON
W2-Tstat
MV
29509
R
W2 - Thermostat
W2 - Thermostat Displays the thermostat call for stage
2 heating 0 = OFF 1 = ON
G-Tstat
MV
29511
R
G - Thermostat
G - Thermostat
Displays the thermostat call of supply
fan 0 = OFF 1 = ON
Occ-Tstat
MV
29512
R
OCC
Occupancy Input
Displays the status of the occupancy
input
0 = disabled/UNOCC
1 = enabled/OCC)
Tstat-Only
MV
29514 R/W
Tstat-Only
Thermostat Only
Control Enabled
A BAS command that allows control
of unit by thermostat
0= NO 1 = YES
OccSrc
MV
29515
R
OccSrc
Occupancy Input
Source
Displays the OCC/UNOCC status
with the selected input source
0 = local input
1 = local network sensor
2 = BAS network request
3 = local schedule
4 = temporary occupancy
Table 32: BACnet Points List (Continued)