Figure 42: Controller–Network Menu
When the unit is BACnet IP, attach a BACnet IP card
and configure the parameters shown in
.
When the unit is BACnet MS/TP, remove the BACnet
IP communication card and configure FC bus comm
mode. Possible selections include: wired field bus,
wireless field bus, N2 field bus, and Modbus field bus
For BACnet MS/TP, configure the parameters shown in
.
Table 27: Cable Recommendations for BACnet MS/TP, Modbus, and N2
Bus and Cable Type
Non-Plenum Applications
Plenum Applications
Part Number
OD
Part Number
OD
FC Bus:
22 AWG Stranded, 3-Wire
Twisted Shielded Cable
1
Anixter: CBL-22/3-FC-PVC
Belden
®
: B5501FE
0.138 inch
Anixter: CBL-22/3-FC-PLN
Belden: B6501FE
0.140 inch
SA Bus (Terminal Block):
22 AWG
Stranded, 4-Wire, Two Twisted Pair
Shielded Cable
1
Anixter: CBL-22/2P-SA-PVC
Belden: B5541FE
0.209 inch
Anixter: CBL-22/2P-SA-PLN
Belden: B6541FE
0.206 inch
NOTE:
1. For best performance, it is strongly recommended to use a 3-wire, two twisted pair, 22 AWG stranded, shielded cable. A 22 gauge cable
offers the best performance for various baud rates, cable distances, and number of trunk devices primarily due to lower conductor-to-
conductor capacitance. Shielded cable offers better overall electrical noise immunity than non-shielded cable.
Table 28: BACnet IP Settings
User Action or Recommended Setting
Description
BACnet IP – Dynamic
IP Address
BACnet IP – Static IP
Address
Default/Range
DHCP
Enabled
IP address may change and may
need to rediscover the router if the
DHCP is enabled
TRUE
FALSE
NA
Device OID
The device ID is the instance number
for the BACnet device. This number
must be unique across the building
networks for all device instances
Set to the device OID
reserved for the unit
Set to the device OID
reserved for the unit
0–4194302
Static IP
Address
This IP address is used when DHCP
enabled is false
(not used)
Set to the IP address
designated for the unit
0.0.0.0 to
255.255.255.255
Static IP
Mask
This IP mask is used when DHCP
enabled is false
(not used)
Set to the IP mask for
the site
0.0.0.0 to
255.255.255.255
Static IP
Router
Address
This IP router address is used when
DHCP enabled is false
(not used)
Set to the router IP
address for the site
0.0.0.0 to
255.255.255.255
IP Address Read-only status of the IP address
in use
Read-only status of the
IP address in-use
Read-only status of the
IP address in-use
0.0.0.0 to
255.255.255.255
LED Main Control Board Status Description
•
PWR –
LED is always ON (solid green) when
power is applied
•
FLT –
LED has a slow red flash when booting up
and fast red flashes when the unit is in FLT mode
•
SA, MOD, EQ, FC –
LEDs blink green when com-
municating
•
LNK –
LEDs blink green when ETH1/ETH2 are
connected to an Ethernet switch
•
ACT –
LEDs blink green when ETH1/ETH2 are
communicating
Setting Up Device Parameters
The local display or MAP gateway is used to configure
the communication parameters of the unit controller.
The key parameters are located in the
Controller > Net-
work