VS-616PS5 Programming Manual
17
B4
Delay Timers
Use the inverter input (multifunction inputs) and output (multifunction outputs) in
place of an external timer. When a multi-function contact input (
H1-XX
= “18”) is
closed, a multi-function contact output (
H2-XX
= “12”) can be set to close after the
On-delay time (
B4-01
) has expired. This function operates independently of any con-
current inverter activity.
Setting Range:
0.0 to 300.0s
Factory Default:
0.0s
Sets the ON-delay time in units of 0.1 second. The multi-function input must be
“closed” for longer than the ON-delay timer for the multi-function output to close.
Setting Range:
0.0 to 300.0s
Factory Default:
0.0s
Sets the OFF-delay time in units of 0.1 second. The multi-function input must be
“open” longer than the OFF-delay timer for the multi-function output to open.
B4-01 On-delay Timer
A
B4-02 Off-delay Timer
A
Multi-function Contact
Input: Timer Function
Multi-function Contact
Output: Timer Function
ON
ON
B4-01
Figure 8 Timing Diagram of Timer Function
B4-01
B4-02
ON ON ON
ON
ON ON ON
ON
B4-02
Section B: Application Parameters
B4 Delay Timers