72
VS-616PS5 Programming Manual
• Overtorque Detection 1 - N.C. (setting: “17”)
Opens during overtorque detection 1 (L6-01, see section
L6
,
Overtorque Detec-
tion
, on page 81).
• Overtorque Detection 2 - N.O. (setting: “18”)
Closes during overtorque detection 2 (L6-01, see section
L6
,
Overtorque Detec-
tion
, on page 81).
• Overtorque Detection 2 - N.C. (setting: “19”)
Opens during overtorque detection 2 (L6-01, see section
L6
,
Overtorque Detec-
tion
, on page 81).
• During Reverse Run (setting: “1A”)
Closes during a reverse run command.
• Baseblock 2 - N.C. (setting: “1B”)
Opens when the inverter output shuts OFF.
• Monitoring/Regenerating Mode (setting: “1D”)
Closes during regenerative operation.
• Automatic Restart (setting: “1E”)
Closes during automatic restart operation.
• OL1 Pre-alarm (setting: “1F”)
Closes when the motor-calculated electronic thermal overload value increases to
90% of the internal fault detection level.
• OH Pre-alarm (setting: “20”)
Closes when the heatsink temperature exceeds the Overheat Temperature Level
(L8-02)
, or when a multi-function contact input (
H1-XX
= “B”) closes.
Detection Width 1
(L4-04)
Output Speed
Frequency
ON
Detection Level 1
(L4-03)
Figure 45 Speed Detection 2 Signal Timing Diagram
Detection 4 Signal
OFF
OFF
Section H: Control Circuit Terminal Parameters
H2 Digital Outputs