58
VS-616PS5 Programming Manual
F8
PG Option Set-up 2
Setting Range:
0,1
Factory Default:
1
Selects the speed feedback method (hall sensor or line drive encoder).
Setting Range:
0 - 50
Factory Default:
0
Sets the number of scans the Pulse Train reference is averaged. A larger number will
provide a more stable speed reference signal, however, the inverter response to a
rapid change in reference may be slower.
A setting of “0” or “1” means no moving average will be used, and the pulse train ref-
erence will be updated every scan.
F8-01 Speed Feedback Detection Method
Q
Setting
Description
0
Speed feedback comes from channels A & B on PG-P2 option
1
Speed feedback comes from channels HS4 & HS5 input on PG-P2 option
F8-01 Pulse Train Average Value
B
Section F: Option Parameters
F8-01 Speed Feedback Detection Method