34
VS-616PS5 Programming Manual
C7
S-Curve Accel/Decel
An S-curve pattern is used to reduce shock and provide smooth transitions during machine
acceleration and deceleration. S-curve characteristic time is the time it takes to reach the set
accel/decel rate during a speed change.
Setting Range:
0.00 to 2.50s
Factory Default:
0.00s
.
The following figure shows FWD/REV run switching with deceleration to stop.
C7-01 S-Curve Time at Acceleration Start
A
C7-02 S-Curve Time at Acceleration End
A
C7-03 S-Curve Time at Deceleration Start
A
C7-04 S-Curve Time at Deceleration End
A
Output Frequency
Frequency Reference
Output Frequency
S-curve Characteristic
Time
Time (Tsc)
Figure 15 S-curve Characteristic Timing Diagram
FWD Run Command
REV Run Command
Output Frequency
C7-02
C7-03
C7-01
C7-04
DC Injection Braking
Time at Stop
B2-04
Figure 16 S-curve Characteristics - FWD/REV Operation
C7-01
C7-02
C7-03
C7-04
Time to accelerate from the minimum frequency
to the maximum frequency (total acceleration)
=
C1-XX
+ (
C7-01
+
C7-02
)/2
Section C: Tuning Parameters
C7 S-Curve Accel/Decel