106
VS-616PS5 Programming Manual
F1-04 PG deviation detection stopping method
0: Ramp to Stop
2: Fast-Stop
1: Coast to Stop
3: Alarm Only
-
0~3
3
B
F1-05 PG rotation selection
0: CCW
1: CW
-
0/1
1
Q
F1-08 Overspeed detection level
%
0~120
115
A
F1-09 Overspeed detection time
s
0~2.0
0.0
A
F1-10 PG deviation detection level
%
0~50
10
A
F1-11 PG deviation detection time
s
0~10.0
0.5
A
F1-13 PG open phase detection delay time
s
0.0~10.0
3.0
A
F2
A1-14B Setup
F2-01 Bipolar or unipolar input selection
0: 3-channel individual
1: 3-channel additional
-
0/1
0
A
F3
D1-08/DI-16H Setup
F3-01 Digital input option
0: BCD 1%
2: BCD 0.01%
1: BCD 0.1%
7: Binary
-
0~7
0
A
F4
AO-08/AO-12 Setup
F4-01 Analog output Channel 1 selection
1: Speed reference
2: Output frequency
3: Inverter output current
5: Motor speed
6: Output voltage
7: DC bus voltage
8: Output power
9: Torque reference (internal)
15: External terminal 13 input voltage
16: External terminal 14 input voltage
17: External terminal 16 input voltage
18: Motor secondary current (I
q
)
19: Motor excitation current (I
d
)
20: Primary frequency after SFS
21: Speed controller ASR input
22: Speed controller ASR output
27: q Axis current control reference
28: d Axis current control reference
29: Voltage limit control output
30: q Axis current control output
31: d Axis current control output
32: Output voltage reference (V
q
)
33: Output voltage reference (V
d
)
45: External torque reference
46: Torque compensation value
49: Control section software number
50: Speed detection PG counter value
53: PID feedback
-
1~60
5
A
F4-02 Analog output channel 1 gain
-
±300.0
1.0
A
F4-03 Analog output channel 1 bias
%
±109.2
0.0
A
F4-04 Analog output channel 2 selection
(same as F4-01)
-
1~60
3
A
F4-05 Analog output channel 2 gain
-
±300.0
1.0
A
No.
Parameter Description
Unit
Setting Range
Default
Access
Level
User
Setting
Appendix
VS-616PS5 Parameter List