VS-616PS5 Programming Manual
Section H: Control Circuit Terminal Parameters
H2 Digital Outputs
• During Run (setting: “0”)
Closes after a run command is inputted or when the inverter generates output volt-
age.
• Zero-speed (setting: “1”)
Closes when the motor speed is less than the zero-speed level
(B2-01).
• Speed Agree 1 (setting: “2”)
Closes whenever the output speed “agrees” with the speed reference plus or minus
the speed agree detection width
(L4-02)
. This works in both forward
and
reverse
operation.
• Desired Speed Agree 1 (setting: “3”)
Closes whenever the output Speed “agrees” with the Speed Agree Detection Level,
(L4-01)
, plus or minus the Speed Agree Detection Width,
(L4-02)
. This works in
both forward
and
reverse operation.
Detection Width 1
(L4-02)
Output Speed
Speed Agree 1 Signal
ON
Speed Reference
Figure 37 Speed Agree Signal 1 Timing Diagram
OFF
OFF
Detection Width 1
(L4-02)
Output Speed
Desired Speed
ON
Detection Level 1
(L4-01)
Figure 38 Desired Speed Agree 1 Signal Timing Diagram
Agree 1 Signal
OFF
OFF