76
VS-616PS5 Programming Manual
Setting Range:
0.0 to 1000.0%
Factory Default:
100.0%
Sets the terminal 16 input gain level when the reference voltage is 10V, (see Figure
46).
Setting Range:
±100.0%
Factory Default:
0.0%
Sets the terminal 16 input bias level when the reference voltage is 0V, (see Figure
46).
Selects the type of signal input at terminal 14.
The resolution of terminal 14 is 11 bit, plus a sign bit. (10 bit for 4-20mA input).
Note:
To enable terminal 14 for a voltage signal (settings: “0” or “1”), cut
jumper wire J1 on the control printed circuit board. J1 is located on the
bottom left-hand corner of the control board directly behind terminal 13.
Selects the multi-function analog input function for terminal 14 (see Terminal 16 Multi-
function Selection for details).
Setting Range:
0.0 to 1000.0%
Factory Default:
100.0%
Sets the terminal 14 input gain level when the reference current is 20mA, (see Figure
46).
H3-06 Terminal 16 Reference % Gain
A
H3-07 Terminal 16 Reference ±% Bias
A
H3-08 Terminal 14 Signal Selection
A
Setting
Description
0
0 to 10V input
1
-10V to +10V input
2
4 to 20mA
(factory default)
H3-09 Terminal 14 Multi-function Selection
A
H3-10 Terminal 14 Reference % Gain
A
Section H: Control Circuit Terminal Parameters
H3 Analog Inputs