VS-616PS5 Programming Manual
97
O2
Key Selection
Enables/disables the digital operator LOCAL/REMOTE key.
Enables/disables the digital operator STOP key, during operation from the external
terminals and during serial communication.
Setting Range:
00 to FF
Factory Default:
Inverter model dependent, kVA dependent
Sets the inverter capacity, according to the model number. Control parameters with
defaults specific to the inverter’s capacity are set automatically (i.e. carrier frequency,
motor data, etc.). This parameter does
not
need changing, unless the control board
is replaced. When replacing the control board, set parameter 02-04 to the appropriate
value per the following tables and re-initialize with parameter A1-03.
230 V Models
O2-01 Local/Remote Key
B
Setting
Description
0
Local/Remote key is disabled.
1
Local/Remote key is enabled
(factory default)
.
Depressing the Local/Remote key switches operation commands
between the digital operator and the settings of
B1-01
&
B1-02
.
O2-02 STOP Key During External Terminal Operation
B
Setting
Description
0
The digital operator STOP key is disabled when Run command does
not
come from the digital operator
(factory default)
.
1
The digital operator STOP key is always enabled.
The STOP key is enabled even during external terminal operation and
serial communication.
O2-04 Inverter Model Selection
A
Model
20P4
20P7
21P5
22P2
23P7
25P7
27P7
2011
2015
02-04
0
1
2
3
4
5
6
7
8
C6-02
(KHz)
8
8
8
8
8
8
8
8
8
L2-02 (sec)
0.7
1.0
1.0
1.0
2.0
2.0
2.0
2.0
2.0
Section O: Operator Parameters
O2 Key Selection