VS-616PS5 Programming Manual
107
F4-06 Analog output channel 2 bias
-
±109.2
0.0
A
F5
DO-02 Setup
F5-01 DO-02C digital output channel 1 selection
0: During RUN 1
1: Zero speed
2: Fref/Fout agree 1
3: Fref/Set agree 1
4: Frequency detection 1
5: Frequency detection 2
6: Inverter Ready
7: DC bus undervoltage
8: Baseblock 1
9: Option reference
A: Remote operation
B: Torque detection 1 (N.O.)
C: Loss of reference
D: DB overheat
E. Fault
F: Not used
10: Minor fault
11: Reset command active
12: Timer output
13: Fref/Fout agree 2
14: Fref/Set agree 2
15: Frequency detection 3
16: Frequency detection 4
17: Torque detection 1 (N.C.)
18: Torque detection 2 (N.O.)
19: Torque detection 2 (N.C.)
1A: Reverse direction
1B: Baseblock 2
1D: Regenerating
1E: Restart enabled
1F: Overload (OL1)
20: OH prealarm
30: Current/Torque limit
31: Speed limit
37: During RUN 2
-
0~FF
0
A
F5-02 DO-02C digital output Channel 2 selection
(same as F5-01)
-
0~3F
1
A
F6
DO-08 Set-up
F6-01 DO-08 digital output selection
0: 8-channel Individual
1: Binary Output
-
0/1
0
A
F8
PG-P2/H2 Set-up
F8-01 Speed feedback method selection
0: Encoder inputs 1: Hall sensor input
-
0/1
1
Q
F8-02 Pulse train moving average value
0=1 Scan (5msec)
-
0-50
0
B
F9
CP-916 Set-up
F9-01 External fault input level from communication option
-
0/1
0
A
F9-02 External fault from communication level
-
0/1
0
A
F9-03 Operation at external fault input from communication option
0: Ramp to stop
2: Fast-stop
1: Coast to stop
3: Alarm only
-
0~3
1
A
No.
Parameter Description
Unit
Setting Range
Default
Access
Level
User
Setting
Appendix
VS-616PS5 Parameter List