50
VS-616PS5 Programming Manual
Sets the relationship between the motor rotation direction and PG polarity. (Hall sen-
sor HS4 & HS5 or encoder channel A & B).
The motor’s rotation direction applies when viewing the motor shaft from the load
side.
Setting Range:
0 to 120%
Factory Default:
115%
This parameter sets the motor overspeed detection level as a percentage of maxi-
mum output speed
(E1-06)
. Used in conjunction with parameter
F1-09
to sense an
overspeed condition.
Setting Range:
0.0 to 2.0s
Factory Default:
0.0s
Sets the elapsed time from when an overspeed condition is detected to when a fault
(or alarm) occurs.
A fault signal is output to stop operation after the absolute value of the motor speed
exceeds the set value of
F1-08
for the time set to
F1-09
. The stopping method is set
by
F1-03
.
F1-05 PG Rotation Selection
Q
Setting
Description
0
HS5 leads HS4 (channel B leads A) in FWD direction.
1
HS4 leads HS5 (A leads B) in FWD direction (
factory default)
.
F1-08 Overspeed Detection Level
A
F1-09 Overspeed Detection Time
A
Figure 29 Overspeed Detection Timing Diagram
Overspeed Level
(F1-08)
OFF
ON
|
Motor Speed
|
F1-09
Overspeed Fault Signal
0
Section F: Option Parameters
F1 PG Option Set-up