VS-616PS5 Programming Manual
Setting Range:
0.0 to 5.0s
Factory Default:
1.0s
This parameter sets the time to allow the rotor to pull in (align) with the magnetic field
at initial excitation. Pull-in waiting time is set in units of 0.1s.
The current vs. time plot during the magnetic pull-in process is as follows:
B3-05 Magnetic Pull-in Time
A
Operation Status
B3-02 Adjustment
B3-04 Adjustment
B3-05Adjustment
Slow Start
-
Decrease set value
Decrease set value
Insufficient torque, and
“STO” is output
Increase set value.
-
-
Current Value
0
1
2
Time
B3-04
B3-05
B3-02
Section B: Application Parameters
B3 Magnetic Pull-in