VS-616PS5 Programming Manual
13
This parameter determines how the inverter will function when switching from local to
remote operation when the external run command is applied.
1
Baseblock
(factory default)-
No output to motor
2
Run at minimum output speed (E1-08).
3
Zero-speed operation (internal speed reference is set to “0”)
B1-06 LOCAL/REMOTE Run Select
A
Selection
Description
0
Operation is disabled if the external run command is applied
prior to switching from local to remote. The run command
must be removed and re-applied to start operation.
1
Operation is enabled if the external run command is applied
prior to switching from local to remote.(factory default).
Setting
Description
Section B: Application Parameters
B1 Sequence