VS-616PS5 Programming Manual
37
D2
Reference Limits
Setting Range:
0.0 to 110.0%
Factory Default:
100.0%
The speed reference upper limit is set as a percentage of the maximum output speed
(E1-06).
Limits the maximum output speed of the motor.
Setting Range:
0.0 to 100.0%
Factory Default:
0.0%
The speed reference lower limit is set as a percentage of the maximum output speed
(E1-06)
. When a run command is input and the speed reference is less than the
lower limit, operation continues at the speed reference lower limit. However, when
the lower limit is set to less than the minimum output speed
(E1-08)
, operation dis-
continues.
D2-01 Speed Reference Upper Limit
B
D2-02 Speed Reference Lower Limit
B
D2-01
Set Frequency Reference
Internal
Speed
Reference
D2-02
Figure 25 Setting Frequency Upper and Lower Limits
100
0
E1-06
%
Hz
Section D: Reference Parameters
D2 Reference Limits