Selects whether a fault contact output is activated during automatic restart.
A setting of “0” will energize the fault relay only after the number of restart attempts as
programmed in parameter L5-01 has been exhausted.
A setting of “1” will energize the fault relay upon every fault. Thus, the fault contact
will energize and then de-energize as the restart procedure is occurring.
L5-02 Automatic Restart Operation Selection
B
Setting
Description
0
No fault relay
(factory default)
.
1
Fault relay is active.
Section L: Protection Parameters
L5 Fault Reset