5
-46
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration
stopped, frequency on hold)
Yes
Yes
Yes
Yes
6-80
B
OH2 alarm signal input (ON: OH2 will be displayed)
Yes
Yes
Yes
Yes
-
C
Multi-function analog input selection (ON: Enable)
Yes
Yes
Yes
Yes
-
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f
control)
No
Yes
No
No 6-136
E
Speed control integral reset (ON: Integral control disabled)
No
Yes
No
Yes 6-136
F
Not used (Set when a terminal is not used)
-
-
-
-
-
10
Up command (Always set with the down command)
Yes
Yes
Yes
Yes
6-81
11
Down command (Always set with the up command)
Yes
Yes
Yes
Yes
6-81
12
FJOG command (ON: Forward run at jog frequency d1-17)
Yes
Yes
Yes
Yes
6-86
13
RJOG command (ON: Reverse run at jog frequency d1-17)
Yes
Yes
Yes
Yes
6-86
14
Fault reset (Reset when turned ON)
Yes
Yes
Yes
Yes
7-2
15
Emergency stop. (Normally open condition: Deceleration to stop in decelera-
tion time set in C1-09 when ON.)
Yes
Yes
Yes
Yes
6-24
16
Motor switch command (Motor 2 selection)
Yes
Yes
Yes
Yes
-
17
Emergency stop (Normally closed condition: Deceleration to stop in deceler-
ation time set in C1-09 when OFF)
Yes
Yes
Yes
Yes
6-24
18
Timer function input (Functions are set in b4-01 and b4-02 and the timer
function outputs are set in H1-
and H2-
.)
Yes
Yes
Yes
Yes
6-107
7-18
19
PID control disable (ON: PID control disabled)
Yes
Yes
Yes
Yes 6-111
1A
Accel/Decel time 2
Yes
Yes
Yes
Yes
6-26
1B
Constants write enable (ON: All constants can be written-in. OFF: All con-
stants other than frequency monitor are write protected.)
Yes
Yes
Yes
Yes 6-154
1C
Trim control increase (ON: d4-02 frequency is added to analog frequency
reference.)
Yes
Yes
Yes
Yes
6-84
1D
Trim control decrease (ON: d4-02 frequency is subtracted from analog fre-
quency reference.)
Yes
Yes
Yes
Yes
6-84
1E
Analog frequency reference sample/hold
Yes
Yes
Yes
Yes
6-85
20 to
2F
External fault (Desired settings possible)
Input mode: NO contact/NC contact, Detection mode: Normal/during opera-
tion
Yes
Yes
Yes
Yes
6-87
30
PID control integral reset (reset when reset command is input or when
stopped during PID control)
Yes
Yes
Yes
Yes 6-111
31
PID control integral hold (ON: Hold)
Yes
Yes
Yes
Yes 6-111
32
Multi-step speed reference 4
Yes
Yes
Yes
Yes
-
34
PID soft starter ON/OFF
Yes
Yes
Yes
Yes 6-111
35
PID input characteristics switch
Yes
Yes
Yes
Yes 6-111
60
DC injection braking command (ON: Performs DC injection braking)
Yes
Yes
Yes
Yes
6-23
61
External search command 1 (ON: Speed search from maximum output fre-
quency)
Yes
No
Yes
No
6-69
62
External search command 2 (ON: Speed search from set frequency)
Yes
No
Yes
No
6-69
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor