5
-50
H3-08
Signal level
selection
(terminal
A2)
0: 0 to +10V, with lower
limit
1:
without
lower limit
2: 4 to 20 mA.
Switch current and voltage
input using the switch on the
control panel.
0 to 2
2
No
A
A
A
A
417H
6-35
6-129
H3-09
Multi-func-
tion analog
input
(terminal
A2) func-
tion selec-
tion
Select multi-function analog
input function for terminal
A2. Refer to the next table.
0 to 1F
0
No
A
A
A
A
418H
6-35
6-129
H3-10
Gain
(terminal
A2)
Sets the input gain (level)
when 10 V (20 mA) is input.
Set according to the 100%
value for the function set for
H3-09.
0.0 to
1000.0
100.0%
Yes
A
A
A
A
419H
6-35
6-129
H3-11
Bias
(terminal
A2)
Sets the input gain (level)
when 0 V (4 mA) is input.
Set according to the 100%
value for the function set for
H3-09.
-100.0
to
+100.0
0.0%
Yes
A
A
A
A
41AH
6-35
6-129
H3-12
Analog
input filter
time con-
stant
Sets primary delay filter time
constant in seconds for the
analog input terminal.
Effective for noise control
etc.
0.00 to
2.00
0.00
s
No
A
A
A
A
41BH 6-36
0.03
s
H3-13
Terminal
A1/A2
switching
0: Use terminal A1 analog
input as main speed fre-
quency reference.
1: Use terminal A2 analog
input as main speed fre-
quency reference.
Effective when H3-09 is set
to 2 and H3-05 is not set to 0
or 2.
0 or 1
0
No
A
A
A
A
41CH
-
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
0 to ±10V,