Conformance to UL Standard
10-
11
10
Conformance to UL Standard
To comply with UL standard, follow the appropriate installation instructions.
Installation Site
Install the Inverter in a pollution degree 2 environment or equivalent.
Specification of Closed-Loop Connector
The closed-loop connectors must be installed on conductors before installing to terminal blocks.
Use JST or equivalent closed-loop connectors shown below.
Control Circuit Terminal
The Class 2 power supply must be used for the control circuits. See below table.
Table 10.2 JST Closed-Loop Connector Model
Inverter
Model CIMR-F7
JST Kit P/N
Input
Output
2011
14-5
14-5
2015
38-6
22-6
2018
38-8
38-8
2022
60-8
38-8
2030
60-8
60-8
2037
100-10
100-10
2045
150-10
150-10
2055
60-10 (2perPh)
60-10 (2perPh)
2075
100-10 (2perPh)
80-10 (2perPh)
2090
150-12 (2perPh)
100-12 (2perPh)
2110
150-12 (2perPh)
150-12 (2perPh)
4022
22-6
14-6
4030
38-6
22-6
4037
38-8
38-8
4045
60-8
60-8
4055
70-8
70-8
4075
100-10
80-10
4090
60-10 (2perPh)
100-10
4110
70-10 (2perPh)
60-10 (2perPh)
4132
70-10 (2perPh)
70-10 (2perPh)
4160
80-12 (2perPh)
80-12 (2perPh)
4185
150-16 (2perPh)
150-16 (2perPh)
4220
325-16 (2perPh)
200-16 (2perPh)
4300
150-16 (4perPh)
150-16 (4perPh)