5
-86
Con-
stant
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
18.5
22
30
37
45
55
75
90
110
132
o2-04
kVA selection
-
2A
2B
2C
2D
2E
2F
30
31
32
33
b8-03
Energy-saving filter time
constant
s
0.50 (Open loop vector control)
2.00 (Open loop vector control)
b8-04
Energy-saving coeffi-
cient
-
115.74
103.58
92.54
76.32
71.56
67.20
46.20
38.91
36.23
32.79
C6-01
CT/VT selection
-
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
C6-02
Carrier frequency selec-
tion (when VT is
selected)
*1 *3
-
6
*2
6
*2
4
*2
4
*2
4
*2
4
*2
3
*2
3
*2
3
*2
2
*2
-
Carrier frequency selec-
tion upper limit (when
VT is selected)
*1
-
6
6
6
6
6
6
4
4
4
4
E2-01
(E4-01)
Motor rated current
A
32.9
38.6
52.3
65.6
79.7
95.0
130.0
156.0
190.0
223.0
E2-02
(E4-02)
Motor rated slip
Hz
1.67
1.70
1.80
1.33
1.60
1.46
1.39
1.40
1.40
1.38
E2-03
(E4-03)
Motor no-load current
A
7.8
9.2
10.9
19.1
22.0
24.0
36.0
40.0
49.0
58.0
E2-05
(E4-05)
Motor line-to-line resis-
tance
Ω
0.403
0.316
0.269
0.155
0.122
0.088
0.092
0.056
0.046
0.035
E2-06
(E4-06)
Motor leak inductance
%
20.1
23.5
20.7
18.8
19.9
20.0
20.0
20.0
20.0
20.0
E2-10
Motor iron loss for
torque compensation
W
508
586
750
925
1125
1260
1600
1760
2150
2350
L2-02
Momentary power loss
ridethru time
s
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
Min. baseblock (BB)
time
s
1.0
1.0
1.1
1.1
1.2
1.2
1.3
1.5
1.7
1.7
L2-04
Voltage recovery time
s
0.6
0.6
0.6
0.6
0.6
1.0
1.0
1.0
1.0
1.0
L8-02
Overheat pre-alarm level
°
C
98
78
85
85
90
90
98
108
100
110
N5-02
Motor acceleration time
s
0.317 0.355 0.323 0.320 0.387 0.317 0.533 0.592 0.646 0.673