User Constant Tables
5-
33
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The V/f control factory settings are given.
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. E1-13 is set to the same value as E1-05 by autotuning.
* 5. When C6-01 = 1, the upper limit is 400.0.
* 6. When C6-01 = 0, the upper limit is 150.0.
E1-11
Mid.
output
frequency
2
Set only to fine-adjust V/f for
the output range. Normally, this
setting is not required.
0.0 to
400.0
*6
0.0 Hz
*3
No
A
A
A
A
30AH 6-122
0.0 to
300.0
*5
E1-12
Mid.
output
frequency
voltage 2
0.0 to
255.0
*1
0.0 V
*3
No
A
A
A
A
30BH 6-122
E1-13
Base
voltage
0.0 to
255.0
*1
0.0 V
*4
No
A
A
Q
Q
30CH 6-122
Con-
stant
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor