User Constant Tables
5-
79
Fault Trace: U2
User constants for error tracing are shown in the following table.
Note 1. The following faults are not included in the fault trace: CPF00, 01, 02, 03, UV1, and UV2.
2. If the PUF fault is already indicated in U2-xx or U3-xx, even if the PUF fault is detected again, the fault trace is not updated. (SPEC: E or later only)
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
U2-01
Current
fault
The contents of the current
fault.
(Cannot be output.)
-
A
A
A
A
80H
U2-02
Previous
fault
The contents of the error that
occurred just prior to the cur-
rent fault.
-
A
A
A
A
81H
U2-03
Reference
frequency at
fault
The reference frequency when
the previous fault occurred.
0.01
Hz
A
A
A
A
82H
U2-04
Output fre-
quency at
fault
The output frequency when the
previous fault occurred.
0.01
Hz
A
A
A
A
83H
U2-05
Output cur-
rent at fault
The output current when the
previous fault occurred.
0.1
A
A
A
A
A
84H
U2-06
Motor speed
at fault
The motor speed when the pre-
vious fault occurred.
0.01
Hz
No
A
A
A
85H
U2-07
Output volt-
age refer-
ence at fault
The output reference voltage
when the previous fault
occurred.
0.1
V
A
A
A
A
86H
U2-08
DC bus
voltage at
fault
The main current DC voltage
when the previous fault
occurred.
1 V
A
A
A
A
87H
U2-09
Output
power at
fault
The output power when the pre-
vious fault occurred.
0.1
kW
A
A
A
A
88H
U2-10
Torque ref-
erence at
fault
The reference torque when the
previous fault occurred. The
motor rated torque corresponds
to 100%.
0.1% No
No
A
A
89H
U2-11
Input termi-
nal status at
fault
The input terminal status when
the previous fault occurred.
The format is the same as for
U1-10.
-
A
A
A
A
8AH
U2-12
Output ter-
minal status
at fault
The output terminal status when
the previous fault occurred. The
format is the same as for U1-11.
-
A
A
A
A
8BH
U2-13
Operation
status at
fault
The operating status when the
previous fault occurred. The
format is the same as for U1-12.
-
A
A
A
A
8CH
U2-14
Cumulative
operation
time at fault
The operating time when the
previous fault occurred.
1
hr
A
A
A
A
8DH