Continuing Operation
6-
69
* 1. The factory setting will change when the control method is changed. The V/f control factory settings are given.
* 2. The factory settings depend upon the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 3. When C6-01=1, the upper limit is 120 %.
Multi-function Contact Inputs (H1-01 to H1-06)
b3-14
Rotation
direction
search selec-
tion
0: Disabled (operates with
specified rotation direction)
1: Enabled (operates with rota-
tion direction found by
search)
0 or 1
1
No
A
A
A
No
19EH
b3-17
Speed search
retrial cur-
rent level
Sets the current level to retry a
speed search as a percentage,
taking the Inverter rated current
as 100%.
0 to 200
150%
*
3
No
A
No
A
No
1F0H
b3-18
Speed search
retrial detec-
tion time
Sets the time for detection in a
speed search retrial in units of
seconds.
0.00 to
1.00
0.01 s
No
A
No
A
No
1F1H
b3-19
Number of
speed search
retrials
Sets the number of times that a
speed search can be retried.
0 to 10
0
No
A
No
A
No
1F2H
L2-03
Min. base-
block time
Sets the Inverter's minimum
baseblock time in units of one
second, when the Inverter is
restarted after power loss ride-
through.
Sets the time to approximately
0.7 times the motor secondary
circuit time constant.
When an overcurrent or over-
voltage occurs when starting a
speed search or DC injection
braking, increase the set values.
0.1 to
5.0
0.2 s
*2
No
A
A
A
A
487H
L2-04
Voltage
recovery time
Sets the time required to return
the Inverter output voltage to
normal voltage at the comple-
tion of a speed search, in units of
one second.
Sets the time required to recover
from 0 V to the maximum volt-
age.
0.0 to
5.0
0.3 s
*2
No
A
A
A
A
488H
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
61
External search command 1
OFF: Speed search disabled (Start from lowest output frequency)
ON: Speed estimation (Estimate the motor speed, and start search from estimated speed)
Current detection (Start speed search from maximum output frequency)
Yes
No
Yes
No
62
External search command 2
OFF: Speed search disabled (Start from lowest output frequency)
ON: Speed estimation (Estimate the motor speed, and start search from estimated speed) (Same
operation as external search command 1)
Current detection: Start speed search from set frequency (reference frequency when search
command was input).
Yes
No
Yes
No
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor