5
-48
4
Frequency (FOUT) detection 1 (ON: +L4-01
≥
output frequency
≥
-L4-01,
L4-02 used)
Yes
Yes
Yes
Yes
6-54
5
Frequency (FOUT) detection 2 (ON: Output frequency
≥
+L4-01 or output
frequency
≤
-L4-01, L4-02 used)
Yes
Yes
Yes
Yes
6-54
6
Inverter operation ready
READY: After initialization, no faults
Yes
Yes
Yes
Yes
-
7
During DC bus undervoltage (UV) detection
Yes
Yes
Yes
Yes
-
8
During baseblock (ON: during baseblock)
Yes
Yes
Yes
Yes
-
9
Frequency reference selection (ON: Frequency reference from Operator)
Yes
Yes
Yes
Yes
-
A
Run Command selection status (ON: Run Command from Operator)
Yes
Yes
Yes
Yes
-
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/under-
torque detection at ON)
Yes
Yes
Yes
Yes
6-57
C
Loss of frequency reference (Effective when 1 is set for L4-05)
Yes
Yes
Yes
Yes
6-74
D
Braking resistor fault (ON: Resistor overheat or braking transistor fault)
Yes
Yes
Yes
Yes
6-76
E
Fault (ON: Digital Operator communications error or fault other than CPF00
and CPF01 has occurred.)
Yes
Yes
Yes
Yes
-
F
Not used. (Set when the terminals are not used.)
-
-
-
-
-
10
Minor fault (ON: Alarm displayed)
Yes
Yes
Yes
Yes
-
11
Fault reset command active
Yes
Yes
Yes
Yes
-
12
Timer function output
Yes
Yes
Yes
Yes 6-107
13
Frequency agree 2 (L4-04 used)
Yes
Yes
Yes
Yes
6-54
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and
during frequency agree)
Yes
Yes
Yes
Yes
6-54
15
Frequency detection 3 (ON: Output frequency
≤
L4-03, L4-04 used)
Yes
Yes
Yes
Yes
6-54
16
Frequency detection 4 (ON: Output frequency
≥
L4-03, L4-04 used)
Yes
Yes
Yes
Yes
6-54
17
Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at
OFF)
Yes
Yes
Yes
Yes
6-57
18
Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at
ON)
Yes
Yes
Yes
Yes
6-57
19
Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at
OFF)
Yes
Yes
Yes
Yes
6-57
1A
During reverse run (ON: During reverse run)
Yes
Yes
Yes
Yes
-
1B
During baseblock 2 (OFF: During baseblock)
Yes
Yes
Yes
Yes
-
1C
Motor selection (Motor 2 selected)
Yes
Yes
Yes
Yes
-
1D
During regeneration (ON: During regeneration)
No
No
No
Yes
-
1E
Restart enabled (ON: Restart enabled)
Yes
Yes
Yes
Yes
6-74
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the
detection level)
Yes
Yes
Yes
Yes
6-61
6-89
20
Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)
Yes
Yes
Yes
Yes
6-89
30
During torque limit (current limit) (ON: During torque limit)
No
No
Yes
Yes
-
31
During speed limit (ON: During speed limit)
No
No
No
Yes
6-89
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor