3.2 Servo Commands
3.2.5 Turn Sensor OFF Command (SENS_OFF: 24h)
3
Main Command
s
3-31
3.2.5
Turn Sensor OFF Command (SENS_OFF: 24h)
Data Format
Phases in which the
Command can be Executed
2, 3
Command
Classification
Common
command
Asynchronous
command
Processing Time
Within 2 s
Subcommand
Cannot be used
Byte
SENS_OFF
Description
Command
Response
0
24h
24h
•
The SENS_OFF command is the sensor power OFF
request command. It is used to turn OFF the power to
the sensor.
•
Confirm the completion of the command execution by
checking that RCMD = SENS_OFF (= 24h) and
CMD_STAT.CMDRDY = 1.
•
CPRM_SEL_MON1/CPRM_SEL_MON2:
Monitor data can be selected by changing the common
parameter setting. Refer to the following chapter for
details.
•
When an absolute encoder is used the position data is
indefinite. "0" is set for POS_RDY.
The coordinate reference point setting becomes invalid
and the ZPOINT (zero point position) and software limit
also become invalid.
•
When an incremental encoder is used, only a response
is returned without processing.
In the following case, an alarm will occur and the com-
mand will not be executed.
•
In the servo ON state: CMD_ALM = Ah (A.95A)