3.1 Common Commands
3.1.3 Setup Device Command (CONFIG: 04h)
3-12
Command Parameters
CONFIG_MOD: Configuration mode
0: Parameter re-calculation and setup, processing time: 5 seconds or less
1: Not supported (CMD_ALM = 9h (A.94B))
2: Initialization to the factory-set parameter setting values, processing time: 20 seconds or less
Turn the power OFF after completion of the process and turn it back ON.
State of Each Status during CONFIG Command Execution
The following tables show the state of each status before, during and after CONFIG command
processing.
When Re-calculating and Setting up the Parameters
When Initializing to the Factory-set Parameter Settings
Status and Output Signal
Before CONFIG Pro-
cessing
During CONFIG Pro-
cessing
After CONFIG Pro-
cessing
ALM
Current state
Current state
Current state
CMDRDY
1
0
1
M_RDY
Current state
Indefinite
Current state
Other Statuses
Current state
Indefinite
Current state
ALM (CN1 Output Signal)
Current state
Current state
Current state
/S-RDY (CN1 Output Signal)
Current state
OFF
Current state
Other Output Signals
Current state
Indefinite
Current state
Status and Output Signal
Before CONFIG Pro-
cessing
During CONFIG Pro-
cessing
After CONFIG Pro-
cessing
ALM
Current state
Current state
Current state
CMDRDY
1
0
1
M_RDY
Current state
0
0
Other Statuses
Current state
Indefinite
Current state
ALM (CN1 Output Signal)
Current state
Current state
Current state
/S-RDY (CN1 Output Signal)
Current state
OFF
OFF
Other Output Signals
Current state
Indefinite
Current state