3.2 Servo Commands
3.2.4 Turn Sensor ON Command (SENS_ON: 23h)
3-30
3.2.4
Turn Sensor ON Command (SENS_ON: 23h)
Data Format
Phases in which the
Command can be Executed
2, 3
Command
Classification
Common
command
Asynchronous
command
Processing Time
Within 2 s
Subcommand
Cannot be used
Byte
SENS_ON
Description
Command
Response
0
23h
23h
•
The SENS_ON command is the sensor information ini-
tialization request command. It initializes the sensor.
•
Confirm the completion of the command execution by
checking that RCMD = SENS_ON (= 23h) and
CMD_STAT.CMDRDY = 1.
•
CPRM_SEL_MON1/CPRM_SEL_MON2:
Monitor data can be selected by changing the common
parameter setting. Refer to the following chapter for
details.
•
When an absolute encoder is used, the initial position is
acquired from the encoder.
The current position is taken to be: acquired encoder
po zero point position offset (common parame-
ter 23).
The coordinate reference point setting is confirmed and
the ZPOINT (zero point position) and software limit
become effective.
•
When an incremental encoder is used, only a response
is returned without processing.