Bit
Hex
Dec
Alarm word
Alarm word 2 Warning word Warning word
2
Extended
Status word
Extended
Status word 2
Alarm Word Extended Status Word
22
00400000
4194304
Fieldbus Fault
(A34)
reserved
Fieldbus Fault
(W34)
reserved
Protection
mode
notification
Sleep Boost
23
00800000
8388608
24 V Supply
Low (A47)
reserved
24V Supply
Low (W47)
reserved
Unused
Running
24
01000000
16777216
Mains Failure
(A36)
reserved
Mains Failure
(W36)
reserved
Unused
Drive Bypass
25
02000000
33554432
1.8V Supply
Low (A48)
Current Limit
(W59)
Current Limit
(A59)
reserved
Unused
Fire Mode
26
04000000
67108864
Brake Resistor
(A25)
reserved
Low Temp
(W66)
reserved
Unused
Pump Protect
(North
America)/
External
Interlock
(International)
27
08000000
134217728
Brake IGBT
(A27)
reserved
Voltage Limit
(W64)
reserved
Unused
Firemode
Limit Exceed
28
10000000
268435456
Option
Change (A67)
reserved
Encoder loss
(W90)
reserved
Unused
FlyStart active
29
20000000
536870912
Drive
Initialized
(A80)
Encoder loss
(A90)
Output freq.
lim. (W62)
BackEMF too
High
Unused
30
40000000
1073741824 Safe Stop
(A68)
PTC
Thermistor
(A74)
Safe Stop
(W68)
PTC Thermist
or (W74)
Unused
31
80000000
2147483648 Mech. brake
low (A63)
Dangerous
failure (A72)
Extended
Status Word
Protection
Mode
7.4 Warnings and alarms
Table 35: Warnings and alarms
Warning/Alarm
Description
Cause
Remedy
1 — 10 V low
The control card voltage is below
10 V from terminal 50.
A short in a connected
potentiometer or improper wiring
of the potentiometer.
Remove the wiring from terminal
50. If the warning clears, the
problem is with the customer
wiring.
2 — Sensor Fault
Note: this warning/alarm is not
available when the MCO301
Programmable API option card is
installed and functioning.
This warning or alarm will only
appear if programmed by the user
in [6–01] Sensor Fault Timeout
Function. The signal on one of the
analog inputs is less than 50% of
the minimum value that is
programmed for that input.
Broken wiring or faulty device
sending the signal.
Check the connections on all the
analog input terminals. Control
card terminals 53 and 54 for
signals, terminal 55 common.
General Purpose I/O Option Card
terminals 11 and 12 for signals,
terminal 10 common. Analog I/O
Option Card terminals 1, 3, 5 for
signals, terminals 2, 4, 6 common.
Check that the frequency converter
programming and switch settings
match the analog signal type.
Perform Input Terminal Signal Test
7 Warnings and alarms
138
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL