Parameter number
Parameter Name
Default Value
Parameter Description
22-50
Under Pressure Function
Off
This parameter configures
the Under Pressure
Function. The Under
Pressure Alarm/Warning is
issued when the system
pressure falls below the
Under Pressure Limit
[22-52] for longer than the
Under Pressure Time Delay
[22-51].
22-51
Under Pressure Delay Time 30 s
This parameter specifies the
time between detection of
an Under Pressure event
and when the action
defined in Under Pressure
Function is issued.
22-52
Under Pressure Difference 10%
Under Pressure Difference
is the difference between
the setpoint and the actual
pressure that will trigger
the Under Pressure
Function. This value is set as
a % of Maximum
Reference/Feedb. [20-14]
5-40
Function Relay
Relay 1: No Alarm
Relay 2: Running
This parameter configures
Relay 1 and 2 functions.
This array parameter allows
configuration of both relays.
See Programming the
controller for details on how
to navigate the array
parameter screen . [0] =
Relay 1, [1] = Relay 2
5-41
On Delay, Relay
Relay 1: 0.01s
Relay 2: 0.01s
This parameter configures
Relay 1 and 2 On Delay
Time. This array parameter
allows configuration of both
relays. See Programming
the controller for details on
how to navigate the array
parameter screen . [0] =
Relay 1, [1] = Relay 2
20-00
Feedback 1 Source
Analog Input 53
Feedback source for the PID
controller, transducer input
source.
20-13
Min Reference/Feedb.
0.0
Minimum feedback value
for the transducer.
20-14
Max Reference/Feedb.
300.0
Maximum feedback value
for the transducer.
3-41
Ramp 1 Ramp Up Time
10 s
Ramp up time (0 to full
speed). Increasing this time
will produce a slower ramp
up.
3-42
Ramp 1 Ramp Down Time 5 s
Ramp down time (full
speed to 0). Increasing this
time will produce a slower
ramp down.
6 Operation
90
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL