Voltage level l, logic ‘1’ PNP
>10 V DC
Voltage level, logic ‘0’ NPN
2)
>19 V DC
Voltage level, logic ‘1’ NPN
2)
<14 V DC
Maximum voltage on input
28 V DC
Input resistance, Ri
Approximately 4 kΩ
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-
voltage terminals.
1
Terminals 27 and 29 can also be programmed as output.
Analog inputs
Number of analog inputs
2
Terminal number
53, 54
Modes
Voltage or current
Mode select
Switches A53 and A54
Voltage mode
Switch A54 = U (left position)
Voltage level
0 V to 10 V (scaleable)
Input resistance Ri
Approximately 10 kΩ
Maximum voltage
±20 V
Current mode
Switch A53 = I (fixed); Switch A54 = I (right position)
Current level
0/4 to 20 mA (scaleable)
Input resistance Ri
Approximately 200Ω
Maximum current
30 mA
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Maximum error 0.5% of full scale
Bandwidth
100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-
voltage terminals.
1
2
3
4
5
9
10
11
7
6
8
1. +24 V
2. 18
3. 37
4. Functional isolation
5. RS485
6. Control
7. PELV isolation
8. High voltage
9. Mains
10.Motor
11.DC-Bus
Figure 99: PELV isolation
Pulse inputs
Programmable pulse inputs
2
9 Technical Specification
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL
155