Parameter number
Parameter Name
Default Value
Parameter Description
20-93
PID Prop Gain
5
Proportional correction gain
for PID controller.
Increasing this value will
produce a faster system
response. CAUTION:
Increasing this value too
high can make the system
unstable and produce
severe oscillations.
20-94
PID Integration Time
3.3 s
Integration time for the PID
controller. Increasing this
value will produce a slower
system response. CAUTION:
Decreasing this value too
low can make the system
unstable and produce
severe oscillations.
Start-Up Genie
This controller is equipped with a Start-Up Genie which allows the user to easily configure
the controller for various pump control applications. The Genie configures parameters
that are based on the selections that are made by the user. The Genie allows the user to
configure the Motor, Application type, inputs, outputs, pump protection features, flow
compensation, and communications. The application types include Single Pump,
Constant Slave, Duplex Control, Speed Control, and test run mode. See the Setup and
Commissioning section for details.
Main menu
The parameters in the Main Menu are grouped by category. Note that some groups are
not visible unless the appropriate option card is installed. The parameter groups in the
Main Menu are shown below.
Parameter Group
Parameter Group Name
0
Operation/Display
1
Load and Motor
2
Brakes
3
Reference/Ramps
4
Limits/Warnings
5
Digital In/Out
6
Analog In/Out
8
Comm. and Options
9
Profibus*
10
CAN Fieldbus*
11
LonWorks*
13
Smart Logic
14
Special Functions
15
Drive Information
16
Data Readouts
18
Info & Readouts
20
Drive Closed Loop
21
Ext. Closed Loop
22
Appl. Functions
6 Operation
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL
91
Summary of Contents for Aquavar
Page 1: ...INSTRUCTION MANUAL IM273 Rev C Aquavar Intelligent Pump Controller 150 HP to 600 HP...
Page 2: ......
Page 171: ......