Number
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
16
Short circuit
X
X
17
Control word timeout (X)
(X)
[8–04] Control
Timeout Function
18
Start Failed
X
[1–77] Compressor
Start Max Speed
[RPM], [1–79]
Compressor Start Max
Time to Trip, [1–03]
Torque Characteristics
20
Temp. Input Error
21
Param error
22
Hoist Mech. Brake
(X)
(X)
Parameter group 2–2*
23
Internal fans
X
24
External fans
X
25
Brake resistor short-
circuited
X
26
Brake resistor power
limit
(X)
(X)
[2–13] Brake Power
Monitoring
27
Brake chopper short-
circuited
X
X
28
Brake check
(X)
(X)
[2–15] Brake Check
29
Heatsink temp
X
X
X
30
Motor phase U
missing
(X)
(X)
(X)
[4–58] Missing Motor
Phase Function
31
Motor phase V
missing
(X)
(X)
(X)
[4–58] Missing Motor
Phase Function
32
Motor phase W
missing
(X)
(X)
(X)
[4–58] Missing Motor
Phase Function
33
Inrush fault
X
X
34
Fieldbus
communication fault
X
X
35
Option fault
36
Mains failure
X
X
37
Phase imbalance (Not
applicable for single
phase drives).
X
38
Internal fault
X
X
39
Heatsink sensor
X
X
40
Overload of Digital
Output Terminal 27
(X)
[5–00] Digital I/O
mode, [5–01]
Terminal 27 Mode
41
Overload of Digital
Output Terminal 29
(X)
[5–00] Digital I/O
mode, [5–02]
Terminal 29 Mode
42
Ovrld X30/6–7
(X)
43
Ext. Supply (option)
45
Earth Fault 2
X
X
46
Pwr. card supply
X
X
47
24 V supply low
X
X
X
7 Warnings and alarms
132
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL
Summary of Contents for Aquavar
Page 1: ...INSTRUCTION MANUAL IM273 Rev C Aquavar Intelligent Pump Controller 150 HP to 600 HP...
Page 2: ......
Page 171: ......