Figure 90: Flow compensation when speed at design working point is unknown
Table 27: Flow compensation parameters when speed at design point is unknown
Parameter Number
Description
Set to
22–80
Flow Compensation
Enabled
22–81
Square-Linear Curve Approximation
Modify between 100% (square) and
0% (linear) per system requirements.
22–82
Work Point Calculation
Enabled — speed at design point is
unknown
22–84
Speed at No Flow [Hz]
To find this point, close all valves in
the system and run the pump at the
minimum head. The speed
corresponding to the minimum head
requirement at no flow will be
entered here. Point A.
22–87
Pressure at No Flow
System pressure at no flow and no
flow speed. This is the minimum
design head. Point A.
22–88
Pressure at Rated Speed
This setting corresponds to the head
developed at design flow and rated
speed. This value can be defined
using the pump performance curve.
Intersects with the design flow to
form point D.
22–89
Flow at Design Point
This setting corresponds to the
system design flow. Intersects with
the pressure at rated speed to form
point D and with the setpoint to form
point B.
22–90
Flow at Rated Speed
This setting corresponds to the flow at
rated speed. This value can be
defined using the pump performance
curve. Intersects with the setpoint to
form point C.
Dual Pump Value Increase
In a Duplex Control System the friction losses can increase when both the lead and lag
pumps are running due to the additional flow in the system. When both pumps are
running, the Rated Curve and Design Curve shown above will change (reach higher flows
at a given pressure) when compared to when a single pump is running. This means that
the settings given to configure the Flow Compensation function may not be accurate
when both pumps are running. The
Dual Pump Value Increase
setting applies an increase
to the setpoint which will offset the additional losses associated with both pumps running.
6 Operation
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL
107