To upload parameters to the LCP without the use of the Start-Up Genie follow the
following procedure:
1. Press [Off] to stop the motor before uploading data.
2. Press [Main Menu] to enter the parameter list.
3. Select [0-**] Operation / Display, press [OK].
4. Use the down arrow to scroll to [0-5*] Copy/Save, press [OK] to enter the submenu.
5. Press [OK] to enable editing of parameter [0-50] LCP Copy.
6. Use the up or down arrows to scroll to ALL to Copy, press [OK] to select.
7. The progress bar will show the status of the process.
8. Press [Status] to return to the main status screen.
9. Press [Auto On] or [Hand On] to resume previous operating mode.
NOTE: Parameter data can be uploaded to the LCP through use of the Start-Up Genie.
Simply select
Copy from LCP
from the setup selection menu at the beginning of the
Genie. Select
All
to copy all parameters from the LCP including size dependent data.
Select
Application Only
to copy all size independent data.
To download parameters to the controller from the LCP without use of the Start-Up Genie
follow the procedure below.
1. Press [Off] to stop the motor before uploading data.
2. Press [Main Menu] to enter the parameter list.
3. Select [0-**]Operation / Display, press [OK].
4. Use the down arrow to scroll to [0-5*]Copy/Save, press [OK] to enter the submenu.
5. Press [OK] to enable editing of parameter [0-50]LCP Copy.
6. To copy all data from the LCP, including size dependent data, use the up or down
arrows to scroll to
All from LCP
, press [OK] to select. To copy all size independent data,
scroll to
Size indep. from LCP
, press [OK] to select.
7. The progress bar will show the status of the process.
8. Press [Status] to return to the main status screen.
9. Press [Auto On] or [Hand On] to resume previous operating mode.
Factory Reset/Initialization
A factory reset or an initialization can be performed to restore the controller back to
default settings. There are multiple ways to perform this function.
Parameter [14-22] Operation Mode can be used to perform the factory reset function.
Using this method does not change controller data such as operating hours, serial
communication selections, fault log, alarm log, and other monitoring functions. To
perform the reset through parameter 14-22 perform the following steps.
1. Press [Main Menu] to enter the parameter list.
2. Use the up and down arrows to scroll to [14-**] Special Functions, press [OK].
3. Use the up and down arrows to scroll to [14-2*] Reset Functions, press [OK].
4. Use the up and down arrows to scroll to [14-22] Operation Mode, press [OK].
5. Press [OK] to enable modification of the parameter.
6. Use the up and down arrows to scroll to
Initialization
, press [OK].
7. Remove input power from the unit and wait for the LCP to turn off.
8. Apply power to the unit. The reset is performed at power up.
9.
Alarm 80 Drive Initialized to Default Value
will be displayed.
10.Press [Reset] to return to operation mode.
Another way to perform the factory reset or initialization is to issue a 3 finger reset. The
process is described below.
1. Remove power from the unit and wait for the LCP to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at the same time. While holding down
the buttons, apply power to the unit.
5 Electrical Installation
82
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL