Start fwd/rev
Start forward and start reverse were selected as functions
for two different digital inputs (parameter group [5–1]*
Digital Inputs). The motor will start in forward or reverse
depending on which corresponding terminal is activated.
Stop
The controller has received a stop command from the
LCP, digital input or serial communication.
Trip
An alarm occurred and the motor is stopped. Once the
cause of the alarm is cleared, the controller can be reset
manually by pressing [Reset] or remotely by control
terminals or serial communication.
Trip lock
An alarm occurred and the motor is stopped. Once the
cause of the alarm is cleared, power must be cycled to the
controller. The controller can then be reset manually by
pressing [Reset] or remotely by control terminals or serial
communication.
LCP parameters
The display configuration shown above represents the default settings. Items 2-6 can be
adjusted to display other values. To display other values, modify parameters [0-20], [0-21],
[0-22], [0-23] or [0-24] which correspond to 2, 3, 4, 5 and 6 respectively.
Menu keys
Table 16: Function description of menu keys
Key
Function
Status
Pressing the [Status] key toggles between different status
screens. There are three different status screens; five
readouts (default), four line readouts or Smart Logic
Control.
• Use the [Status] key for selecting the mode of the LCP
or for changing back to Status Display mode from
any other menu.
• The LCP display contrast can also be adjusted by
pressing [Status] plus [
▲
] or [
▼
] to adjust the
display brightness.
• The symbol in the upper right corner of the display
shows the direction of motor rotation (arrow), which
set-up is active (number) and which is being
programmed (number in parenthesis).
Quick Menu
Pressing the [Quick Menu] key provides access to a set of
submenus that allows easy access to some common
parameters as well as the Start-Up Genie. The Quick
Menu consists of My Personal Menu, Quick Set-up,
Function Set-up, Start-Up Genie, changes made and
Loggings.
Main Menu
Pressing the [Main Menu] key allows access to the
complete parameter set. Press [Main Menu] twice to
access the top level index. Press [Main Menu] once to
return to the last location accessed. Press and hold [Main
Menu] for 5 seconds provides access to the Parameter
Shortcut. The Parameter shortcut allows the user to enter
a parameter number to give direct access to that
parameter.
5 Electrical Installation
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL
79