Maximum terminal load (AC-15)1) on 1–3 (NC) inductive load @ cos
φ
0.4)
240 V AC, 2A
Maximum terminal load (DC-1)1) on 1–3 (NC) (resistive load)
50 V DC, 2A
Maximum terminal load (DC-13)1) on 1–3 (NC) (inductive load)
24 V DC, 0.1A
Minimum terminal load on 1–3 (NC), 1–2 (NO)
24 V DC 10mA, 24 V AC 20mA
Environment according to EN 60664–1
overvoltage category III/pollution degree 2
Relay 02 Terminal number
4–6 (break), 4–5 (make)
Maximum terminal load (AC-2)
1
on 4–5 (NO) (resistive load)
2,3
400 V AC, 2A
Maximum terminal load (AC-15)
1
(Inductive load @ cos
φ
0.4)
240 V AC, 0.2A
Maximum terminal load (DC-1)
1
on 4–5 (NO) (Resistive load)
80 V DC, 2A
Maximum terminal load (DC-13)
1
on 4–5 (NO) (Inductive load)
24 V DC, 0.1A
Maximum terminal load (AC-1)
1
on 4–6 (NC) (Resistive load)
240 V AC, 2A
Maximum terminal load (AC-15)
1
on 4–6 (NC) (Inductive load @ cos
φ
0.4)
240 V AC, 0.2A
Maximum terminal load (DC-1)
1
on 4–6 (NC) (Resistive load)
50 V DC, 2A
Maximum terminal load (DC-13)
1
on 4–6 (NC) (Inductive load)
24 V DC, 0.1A
Minimum terminal load on 1–3 (NC), 1–2 (NO), 4–6 (NC), 4–5 (NO)
24 V DC 10mA, 24 V AC 20mA
Environment according to EN 60664–1
overvoltage category III/pollution degree 2
Wiring for factory default setup
This configuration utilizes the controller factory default settings for I/O. The factory default
settings for IT are configured for a single pump, constant pressure application with a 300
psi, 4-20mA pressure transducer wired to AI 53. A jumper wire is needed between
terminals 29 and 32 to enable the No Water/Loss of Prime Restart function. A Start signal
is applied on Digital Input 18. The controller will receive a Start command when DI 18 is
connected to 24V. There are no parameters that need to be adjusted for this
configuration. Refer to Commissioning section for details on configuring the controller
and changing application settings.
CAUTION:
When a Start (Closed) signal is present on DI18, the controller can start the pump/motor
at any time without warning. Set DI18 to Stop (Open) or press the [Off] operation key
before using the Genie. Apply the Start signal to the controller only when pump/motor
operation is desired.
NOTICE:
The factory default settings are configured to require a start signal wired to DI18 as shown
below.
Figure 75: Required terminal connections for use with factory default settings
5 Electrical Installation
66
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL