9.4 Wire sizing charts
VFD input wire sizing
Maximum allowable conductor length (45°C Ambient, 5% drop)
Line
power
supply
Controller ratings
Conductor size for 75°C rated wire (lengths in bold require 90°C rated wire)
Freque
ncy
conver
ter
HP
rating
Input
current
Wires/
phases
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
3x460
V AC
1500 150
183
2
717
904
1141 1439
2000 250
291
2
905
1143 1439 1699 2040
2500 300
438
2
1204 1421 1706
3000 350
427
2
1158 1390
4000 450
531
4
992
1252 1577 1862 2236 2613 2988 3718
4500 500
580
4
908
1146 1444 1705 2047 2393 2736 3404
5000 550
667
4
997
1256 1483 1780 2080 2379 2960
6000 600
718
4
1167 1377 1654 1933 2210 2749
3x575
V AC
2000 200
189
2
695
875
1104 1393
2500 250
234
2
892
1125 1421 1790 2113 2537
3000 300
286
2
921
1163 1464 1729 2076
3500 350
339
2
1235 1459 1751
4000 400
390
2
1268 1522
4500 450
434
4
962
1214 1532 1930 2279 2736 3197 3656 4549
5000 500
482
4
866
1093 1380 1738 2052 2463 2879 3292 4096
6000 600
549
4
959
1211 1526 1801 2163 2528 2890 3596
VFD output wire sizing
Maximum allowable conductor length (45°C Ambient, 5% drop)
Line
power
supply
Controller ratings
Conductor size for 75°C rated wire (lengths in bold require 90°C rated wire)
Freque
ncy
conver
ter
HP
rating
Input
current
Wires/
phases
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
3x460
V AC
1500 150
190
2
691
870
1099 1386
2000 200
240
2
870
1097
2500 250
302
2
872
1101 1387 1637 1966
3000 300
361
2
1160 1370 1644
3500 350
443
2
1116 1340
4500 450
540
4
975
1231 1551 1831 2199 2570 2939 3656
5000 500
590
4
893
1127 1420 1676 2012 2352 2690 3346
5500 550
678
4
981
1235 1459 1751 2047 2340 2912
6000 600
730
4
1147 1355 1626 1901 2174 2704
9 Technical Specification
162
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL