6.6 Basic operational programming
Required initial frequency converter programming
NOTE: If the Start-Up Genie is run, ignore the following.
Frequency converters require basic operational programming before running for best
performance. Basic operational programming requires entering motor-nameplate data
for the motor being operated and the minimum and maximum motor speeds. Enter data
in accordance with the following procedure. Parameter settings recommended are
intended for start up and checkout purposes. Application settings may vary. See the Local
Control Panel section for detailed instructions on entering data through the LCP.
Enter data with power ON, but before operating the frequency converter.
1. Press [Main Menu] twice on the LCP.
2. Use the navigation keys to scroll to parameter group
0–** Operation/Display
and press
[OK].
Figure 91: Main menu
3. Use navigation keys to scroll to parameter group
0–0* Basic settings
and press [OK].
Figure 92: Operation/display
4. Use navigation keys to scroll to
0–3 Regional Settings
and press [OK].
Figure 93: Basic settings
5. Use navigation keys to select
[0] International
or
[1] North America
as appropriate and
press [OK]. This changes the default settings for a number of basic parameters. See
5.4
International/North American Default Parameter Settings
for a complete list.)
6. Press [Quick Menu] on the LCP.
7. Use the navigation keys to scroll to parameter group
Q2 Quick Setup
and press [OK].
6 Operation
124
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL