Digital I/O
Operating Mode
Terminal Number Parameter
Number
Single Pump/
Constant Slave
Speed Control
Test Run Mode
Description
32
5–14
[1] Restart
[0] No Operation [0] No Operation Configured for
use as a Reset for
the No Water/Loss
of Prime Restart
function for
Single Pump and
Constant Slave
modes. Refer to
the Pump
Protection section
for details.
33
5–15
[23] SP1/SP2
Select
[23] SP1/SP2
Select
[23] SP1/SP2
Select
Digital input.
Configured for
use as a Setpoint
1/Setpoint 2
select (SP1/SP2)
20
—
Common
Common
Common
Common for
digital inputs and
reference for 24 V
supply
Table 29: Digital input functionality based for duplex mode
Digital I/O
Duplex Control Mode
Terminal Number
Parameter Number
Lead
Lag
Description
18
5–10
[8] Start
[8] Start
Start/Stop digital
input signal for the
drive. Connect input
to 24 V to start. Open
the input to stop. This
is a required
connection.
19
5–11
[0] No Operation
[0] No Operation
Unused digital input.
This input can be
configured for use as
a Pump Protect
Warning or Alarm
input. See Pump
Protect section to
enable the Warning
or Alarm associated
with this input.
6 Operation
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL
117