3.6
Analog input
Driver allows connection of external analog signal. Input can be used as velocity or position set point value.
Picture. 11. Analog input 0..10 V
Driver’s analog input range is 0..10 V. Input allows direct connection PLC driver with 0..10 V analog output. In case
of analog input control using potentiometer to its supply can be used encoder supply 5 V (25). Then input
will be operate in its half range. To use full input range it is recommended use external stabilized power supply 10
V.
To minimize noises cables of analog signal should lead as far as possible from motor cables and braking
resistor.
3.7
Programmable outputs
Driver is equipped with two programmable outputs with opto insulation. Before running of outputs please supply
GNDQ (28) and VDDQ (29) terminals. Power supply should be in range 12..24 V.
Picture. 12. Programmable output with opto insulation
Parameters
:
Opto insulation
Constant load max 2 A at 24 V for channel
Voltage range 12..24 V
Build-in protection diode for inductive load