English
74
WILO SE 05/2010
8.7
Menu elements reference
The following table gives an overview of the available elements of all
menu levels. The menu number and the element type are designated
separately, and the function of the element is explained. If applicable,
there is information about the setting options of the individual ele-
ments.
NOTE
A few elements are hidden under certain conditions and are therefore
skipped in the menu navigation.
If, for example, the external setpoint adjustment under menu number
<5.4.1.0> is set to “OFF”, the number <5.4.2.0> will be hidden. Menu
number <5.4.2.0> will only be visible if menu number <5.4.1.0> has
been set to “ON”.
The condition for hiding a menu element is explained in the last col-
umn of the table.
No.
Designation
Type
Symbol Values/explanations
Display conditions
1.0.0.0
Setpoint
Setting/display of the setpoint
(for further information, see
Section 8.6.1 “Adjusting the set-
point” on page 70)
2.0.0.0
Control mode
Setting/display of the control
mode
(for further information, see
Sections 9.4 “Setting the control
mode” on page 82 and 6.2 “Con-
trol modes” on page 55)
Constant speed control
Constant p-c control
Variable p-v control
PID control
3.0.0.0
Pump on/off
ON
Pump switched on
OFF
Pump switched off
4.0.0.0
Information
Information menus
4.1.0.0
Actual values
Display of current actual values
4.1.1.0
Actual values sen-
sor (IN1)
Depending on current control
mode
p-c, p-v: Value H in mWs
PID control: Value in %
Not displayed for manual
control mode
4.1.2.0
Switching fre-
quency
HIGH
High switching frequency (fac-
tory setting)
The switching frequency can
only be changed via the
CAN bus or IR-PDA.
LOW
Low switching frequency
4.1.3.0
Power
Current power input P
1
in watts
4.2.0.0
Operating data
Display of operating data
±
±
±