background image

English

74

WILO SE 05/2010

8.7

Menu elements reference

The following table gives an overview of the available elements of all 
menu levels. The menu number and the element type are designated 
separately, and the function of the element is explained. If applicable, 
there is information about the setting options of the individual ele-
ments.

NOTE
A few elements are hidden under certain conditions and are therefore 
skipped in the menu navigation. 

If, for example, the external setpoint adjustment under menu number 
<5.4.1.0> is set to “OFF”, the number <5.4.2.0> will be hidden. Menu 
number <5.4.2.0> will only be visible if menu number <5.4.1.0> has 
been set to “ON”.

The condition for hiding a menu element is explained in the last col-
umn of the table.

No.

Designation

Type

Symbol Values/explanations

Display conditions

1.0.0.0

Setpoint

Setting/display of the setpoint
(for further information, see 
Section 8.6.1 “Adjusting the set-
point” on page 70)

2.0.0.0

Control mode

Setting/display of the control 
mode
(for further information, see 
Sections 9.4 “Setting the control 
mode” on page 82 and 6.2 “Con-
trol modes” on page 55)

Constant speed control

Constant p-c control

Variable p-v control

PID control

3.0.0.0

Pump on/off

ON
Pump switched on

OFF
Pump switched off

4.0.0.0

Information

Information menus

4.1.0.0

Actual values

Display of current actual values

4.1.1.0

Actual values sen-
sor (IN1)

Depending on current control 
mode 
p-c, p-v: Value H in mWs
PID control: Value in %

Not displayed for manual 
control mode

4.1.2.0

Switching fre-
quency

HIGH
High switching frequency (fac-
tory setting)

The switching frequency can 
only be changed via the 
CAN bus or IR-PDA.

LOW
Low switching frequency

4.1.3.0

Power

Current power input P

1

 in watts

4.2.0.0

Operating data

Display of operating data

±

±

±

Summary of Contents for VeroLine IP-E 40/160-4/2 Series

Page 1: ...win DP E D Einbau und Betriebsanleitung GB Installation and operating instructions F Notice de montage et de mise en service NL Inbouw en bedieningsvoorschriften 2 110 035 Ed 02 2010 05 Wilo Wilo Vero...

Page 2: ...Fig 1 IF Modul Fig 2 L1 L2 L3 PE AUX SSM SBM Ext off MP DDG GND 10V 20mA L H IN2 GND IN1 24V M16 M12 M20 M12 M25 Fig 3...

Page 3: ...Fig 4 20 8 0 mA 0 2 0 3 0 20 10 4 4 5 6 6 4 10 4 0 V 0 1 0 1 5 10 5 2 2 2 8 3 2 1 min 0 nmax nmin pmax pmin off 0 100 off 0 100 mWS 0 1 min 0 nmax nmin pmax pmin mWS 0...

Page 4: ...Fig 5 IP E DP E 6 3 3 3 1 1 12 1 11 1 13 3 2 3 1 1 1 12 1 22 1 21 1 13 1 2 1 3 8 2 7 7 3 7 1 7 5 7 4...

Page 5: ...D Einbau und Betriebsanleitung 3 GB Installation and operating instructions 49 F Notice de montage et de mise en service 95 NL Inbouw en bedieningsvoorschriften 141...

Page 6: ...hreibung und Funktion 8 6 1 Beschreibung des Produkts 8 6 2 Regelungsarten 9 6 3 Doppelpumpenfunktion 10 6 4 Weitere Funktionen 13 7 Installation und elektrischer Anschluss 15 7 1 Installation 15 7 2...

Page 7: ...eit Diese Betriebsanleitung enth lt grundlegende Hinweise die bei Auf stellung und Betrieb zu beachten sind Daher ist diese Betriebsanlei tung unbedingt vor Montage und Inbetriebnahme vom Monteur sowi...

Page 8: ...d oder mangels Wissen benutzt zu werden es sei denn sie werden durch eine f r ihre Sicher heit zust ndige Person beaufsichtigt oder erhielten von ihr Anwei sungen wie das Ger t zu benutzen ist Kinder...

Page 9: ...hgem er Transport kann zu Personensch den f hren Der Transport der Pumpe ist mittels zugelassener Lastaufnahme mittel durchzuf hren Sie sind an den Pumpenflanschen und gege benenfalls am Motor Au endu...

Page 10: ...ung im Freien nicht zul ssig VORSICHT Gefahr von Sachsch den Unzul ssige Stoffe im Medium k nnen die Pumpe zerst ren Abra sive Feststoffe z B Sand erh hen den Verschlei der Pumpe Pumpen ohne Ex Zulass...

Page 11: ...Es wird nicht bei allen Pumpentypen ein Durchflusswert ausgegeben HINWEIS Das Sicherheitsdatenblatt des zu f rdernden Mediums ist in jedem Fall zu beachten Pumpe IP E DP E Einbau und Betriebsanleitun...

Page 12: ...INLINE Bauart ausgef hrt d h saug und druckseitige Flansche liegen in einer Mittellinie Alle Pumpengeh use sind mit Pumpenf en versehen Die Montage auf einen Fundament sockel wird empfohlen Elektronik...

Page 13: ...nmin und nmax gehalten werden Fig 12 Die Betriebsart Steller deaktiviert alle brigen Regelungsarten PID Control Wenn die oben genannten Standard Regelarten nicht anwendbar sind z B bei Hosenrohr Inst...

Page 14: ...ichtung linke Pumpe An dieser Pumpe den Differenzdrucksensor anschlie en DieMesspunktedesDifferenzdrucksensorsderMasterpumpem ssen im jeweiligen Sammelrohr auf der Saug und Druckseite der Doppel pumpe...

Page 15: ...6 4 Weitere Funktionen auf Seite 13 6 3 2 Verhalten im Doppelpumpenbetrieb Pumpentausch Im Doppelpumpenbetrieb erfolgt alle 24h einstellbar ein Pumpen tausch Der Pumpentausch kann intern zeitgesteuer...

Page 16: ...Kommunikationsunterbrechung zeigen beide Displays den Fehlercode E052 F r die Dauer der Unterbrechung verhalten sich beide Pumpen als Einzelpumpen Beide Module melden ber den ESM SSM Kontakt die St ru...

Page 17: ...lben der maximalen F rderh he Netz Aus Netz Ein Wenn w hrend der Kommunikationsunterbrechung am ehemaligen Master der Betrieb durch Netz Aus Netz Ein unterbrochen wird startet der ehemalige Master mit...

Page 18: ...Fehl funktionen verursachen Die Werkseinstellungen sind f r den mit gelieferten Wilo Differenzdrucksensor konfiguriert Einstellwerte Eingang In1 0 10 Volt Druckwertkorrektur ON Wenn der mitgelieferte...

Page 19: ...ung Pumpe ausschlie lich von Fachpersonal installieren lassen VORSICHT Besch digung der Pumpe durch berhitzung Die Pumpe darf nicht l nger als 1 Minute ohne Durchfluss laufen Durch den Energiestau ent...

Page 20: ...tung muss dem Richtungspfeil auf dem Pumpengeh u seflansch entsprechen Das Entl ftungsventil Fig 17 Pos 1 muss immer nach oben zeigen Jede Einbaulage au er Motor nach unten ist zul ssig Das Elektronik...

Page 21: ...uftreten kann Vorbereitung Hinweise Der elektrische Anschluss muss ber eine fest verlegte Netzan schlussleitung erfolgen einzuhaltender Querschnitt min 4 x 1 5 mm2 max 4 x 4 mm2 die mit einer Steckvor...

Page 22: ...er allstromsensiti ver Ausf hrung vom Typ B sind zul ssig Kennzeichnung FI Ausl sestrom 30 mA Stromart und Spannung des Netzanschlusses berpr fen Typenschilddaten der Pumpe beachten Stromart und Spann...

Page 23: ...mpentausch Parametrierbar im Servicemen 5 1 3 2 Die Klemme AUX reagiert auf einen anliegenden Impuls Durch einmaliges berbr cken der beiden Klemmen wird der externe Pumpentausch soweit aktiviert durch...

Page 24: ...rden Dr cken des roten Knopfs dient zur Aktivierung eines ausgew hlten Men ele ments sowie zur Best tigung von Werten DIP Schalter Die DIP Schalter Fig 9 Pos 6 Fig 22 befinden sich unter der Geh useab...

Page 25: ...1 0 Information Ein Men element das Informationen zum Ger testa tus oder Einstellungen darstellt die nicht ge ndert werden k nnen Auswahl Einstellung Ein Men element das Zugriff auf eine ver nderbare...

Page 26: ...kann noch Spannung anliegen Allgemeine Sicherheitshinweise beachten 8 5 1 Statusseite der Anzeige Die Standardansicht in der Anzeige ist die Statusseite Der aktuell ein gestellte Sollwert wird in den...

Page 27: ...n ebene Die neue Men ebene ist im Display durch die Men nummer gekenn zeichnet Z B springt bei R ckkehr von Men ebene 4 1 5 0 die Men nummer auf 4 1 0 0 HINWEIS Wird der rote Knopf 2 Sekunden lang ged...

Page 28: ...lge haben und zu Sachsch den an der Pumpe oder der Anlage f hren Fehler erst nach Beseitigung ihrer Ursache quittieren St rungsbeseitigung nur durch Fachkr fte durchf hren lassen Im Zweifel Hersteller...

Page 29: ...gez hlt Das zum Men element zugeh rige Symbol und der Soll oder Istwert wird ggf angezeigt Wird der abw rts weisende Pfeil f r Ebene tiefer angezeigt roten Knopf dr cken um in die n chst tiefere Men e...

Page 30: ...ie Anzeige auf die Statusseite zur ck Fig 32 8 6 5 Informationen abrufen Bei Men elementen des Typs Information k nnen keine nderun gen vorgenommen werden Sie sind durch das Standardsymbol Zugriffsspe...

Page 31: ...aktivieren deaktivieren Um unzul ssige nderungen an den Einstellungen der Pumpe zu ver hindern kann eine Sperre aller Funktionen aktiviert werden Eine aktive Zugriffssperre wird auf der Statusseite du...

Page 32: ...hnung Typ Symbol Werte Erl uterungen Anzeigebedingungen 1 0 0 0 Sollwert Einstellung Anzeige des Soll werts weitere Informationen siehe Kapitel 8 6 1 Anpassen des Sollwerts auf Seite 24 2 0 0 0 Regelu...

Page 33: ...5 Sekunden 4 2 5 0 Netz Ein Z hler Anzahl der Einschaltvorg nge der Versorgungsspannung jedes Herstellen der Versor gungsspannung nach einer Unterbrechung wird gez hlt 4 2 6 0 Pumpen Kickz h ler Anzah...

Page 34: ...ur angezeigt wenn BMS aktiv ist LON Feldbussystem Wird nur angezeigt wenn BMS aktiv ist CAN Feldbussystem Wird nur angezeigt wenn BMS aktiv ist Gateway Protokoll Wird nur angezeigt wenn BMS aktiv ist...

Page 35: ...Wird nur bei DP MA ange zeigt Externer Pumpentausch Wird nur bei DP MA ange zeigt siehe Klemme AUX 5 1 3 3 Intern Zeitintervall Einstellbar zwischen 8h und 36h in 4h Schritten Wird angezeigt wenn inte...

Page 36: ...Externer Sollwerteingang 2 inaktiv 5 4 2 0 In2 Wertebereich Einstellung des Wertebereichs M gliche Werte 0 10 V 2 10 V 0 20 mA 4 20 mA Wird nicht angezeigt wenn In2 inaktiv 5 5 0 0 PID Parameter Eins...

Page 37: ...tellung Einstellungen werden beim Best tigen nicht ve ndert Wird bei aktiver Zugriffs sperre nicht angezeigt ON Einstellungen werden beim Best tigenauf Werkseinstellung zur ckgesetzt Vorsicht Alle man...

Page 38: ...t unter Druck Je nach Temperatur des F rdermediums und Systemdruck kann beim vollst ndigen ffnen der Entl ftungsschraube extrem hei es oder extrem kaltes F rdermedium in fl ssigem oder dampff rmi gem...

Page 39: ...den Status SL Slave Alle weiteren Einstellungen der Pumpe k nnen ab jetzt nur noch ber den Master erfolgen HINWEIS Die Prozedur kann sp ter manuell durch Anw hlen des Men s 5 1 2 0 gestartet werden In...

Page 40: ...m Soll Wert an den Ausgang des Reglers Das Vorzei chen des P Anteils bestimmt den Wirksinn des Reglers Der I Anteil oder auch integrale Anteil des Reglers integriert ber die Regelabweichung Eine konst...

Page 41: ...ID Regelung nur mit minima ler oder maximaler Drehzahl dreht und nicht auf nderungen der Parameterwerte reagiert ist der Reglerwirksinn zu berpr fen 10 Wartung Sicherheit Wartungs und Reparaturarbeite...

Page 42: ...HR Lebensgefahr Durch Herabfallen der Pumpe oder einzelner Komponenten kann es zu lebensgef hrlichen Verletzungen kommen Pumpenkomponenten bei den Installationsarbeiten gegen Herab fallen sichern 10 2...

Page 43: ...d Wellendichtung in das Pumpengeh use ein setzen und mit den Flanschschrauben Fig 5 Pos 4 befestigen Druckmessleitungen des Differenzdrucksensors montieren Netzanschlussleitung anklemmen Absperrarmatu...

Page 44: ...Mechanische St rungen Fehlertyp Erl uterung Priorit t A endg ltiger Fehler 6 B im 6 Fehlerfall endg ltiger Fehler 5 C Warnung nach 5 min bergang zu einem Fehler im 6 Fehlerfall endg ltiger Fehler 4 D...

Page 45: ...bsenken E021 berlast Motor Betriebspunkt au erhalb des Kennfeldes Betriebspunkt berpr fen korrigieren B A Ablagerungen in der Pumpe Kundendienst anfordern E023 Kurz Erdschluss Motor oder Modul defekt...

Page 46: ...wird E052 DP MP Kommunika tions Timeout Kabel MP Kommunika tion defekt Kabel und Kabelverbindungen berpr fen E E Elektronik fehler E070 interner Kommunika tionsfehler SPI Interner Elekronikfehler Kun...

Page 47: ...kunden Roten Knopf erneut dr cken Der Fehler ist quittiert und die Statusseite wird angezeigt Fig 40 Fehlertyp A Schema 1 2 3 4 Programm schritt abfrage Inhalt 1 Fehlercode wird angezeigt Motor aus Ro...

Page 48: ...angezeigt HINWEIS Die Autoresetzeit kann unter Men nummer 5 6 3 0 eingestellt werden Zeitvorgabe 10 bis 300 s Vorkommen X Y Ist das aktuelle Vorkommen des Fehlers gleich dem Maximalvorkom men Fig 45 R...

Page 49: ...das aktuelle Vorkommen um eins hochgez hlt HINWEIS Durch Beheben der Fehlerursache wird der Fehler automatisch quit tiert Restzeit abwarten Ist das aktuelle Vorkommen x gleich dem Maximalvorkommen des...

Page 50: ...2 4 5 3 6 7 9b 9a 8 Programm schritt abfrage Inhalt 1 Fehlercode wird angezeigt Pumpe geht in den Notbetrieb 2 Fehlerz hler wird erh ht 3 Fehlermatrix AC oder HV 4 SSM wird aktiviert 5 Fehlerkriteriu...

Page 51: ...folgende Tabelle dient der Identifizierung der einzelnen Bauteile Notwendige Angaben bei Ersatzteilbestellungen Ersatzteilnummern Ersatzteilbezeichnungen S mtliche Daten des Pumpen und Motortypenschil...

Page 52: ...escription and function 54 6 1 Description of the product 54 6 2 Control modes 55 6 3 Dual pump function 56 6 4 Other functions 59 7 Installation and electrical connection 61 7 1 Installation 61 7 2 E...

Page 53: ...r agreement this declaration loses its validity 2 Safety These operating instructions contain basic information which must be adhered to during installation and operation For this reason these operati...

Page 54: ...y are supervised by a person responsible for their safety or where they receive instruction from such a person as to how the device is to be operated Children must be kept under supervision in order t...

Page 55: ...NING Danger of personal injury Improper transport can lead to personal injury The pump must be transported using approved load bearing equip ment This is to be attached to the pump flanges and if nece...

Page 56: ...itted for this series CAUTION Risk of material damage Impermissible substances in the fluid can destroy the pump Abra sive solids e g sand increase pump wear Pumps without an Ex rating are not suitabl...

Page 57: ...on every type of pump NOTE Always read and follow the material safety data sheet for the fluid being pumped Pump IP E DP E Installation and operating instructions Property Value Remarks Speed range 7...

Page 58: ...ion i e the flanges on the suction and pressure sides lie along a centre line All pump housings are provided with a pump base Installation on a foundation base is recommended Electronic module The ele...

Page 59: ...speed of the pump can be kept to a constant speed between nmin and nmax Fig 12 Manual control mode deactivates all other con trol modes PID control If the standard control modes mentioned above cannot...

Page 60: ...ssuresensor of the master pump must be on the suction and pressure side of the double pump system in the respective collector pipe InterFace Module IF Module For communication between pumps and the ma...

Page 61: ...n synchronously See Section 6 4 Other functions on page 59 6 3 2 Behaviour in dual pump operation Pump cycling In dual pump operation pump cycling is done every 24 hours config urable Pump cycling can...

Page 62: ...ption of communication both displays show fault code E052 Both pumps behave as single pumps for as long as the interruption lasts Both modules report the malfunction via the ESM SSM contact The slave...

Page 63: ...ion is discontinued due to power cycling mains Off mains On the former master will start up with the latest settings it has from the double pump configuration 6 4 Other functions Disabling or enabling...

Page 64: ...ure value correction ON When using the supplied Wilo differential pressure sensor these settings must not be changed Modifications are only needed if another differential pressure sensor is used Switc...

Page 65: ...t handling Have the pump installed by qualified personnel only CAUTION Damage to the pump due to overheating The pump must not be allowed to operate dry for more than 1 minute Dry running causes a bui...

Page 66: ...not bear the weight of the pipes The direction of flow must correspond to the direction arrow on the pump housing flange The bleed valve Fig 17 Item 1 must always face upwards All installation positio...

Page 67: ...taneous operation of all pumps is possible in multi pump operation Preparation notes The electrical connection must be established via a fixed power cable cross section to be maintained 4 x 1 5 mm2 mi...

Page 68: ...sal current sensitive design are allowed Labelling RCD Trigger current 30 mA Check the current type and voltage of the mains connection Observe the name plate information for the pump The current type...

Page 69: ...p cycling Can be configured in the service menu 5 1 3 2 The AUX terminal responds to the presence of an impulse One time bridging of the two terminals will cause external pumping to take place if it i...

Page 70: ...menu elements and used to change values Pressing the red button activates a selected menu element and confirms values DIP switch The DIP switches Fig 9 Item 6 Fig 22 are located under the housing cov...

Page 71: ...shows information about the device status or settings that cannot be changed Selection setting A menu element that provides access to a changeable setting element with menu number X X X 0 One level up...

Page 72: ...in the display even if is switched off Observe general safety instructions 8 5 1 Display status page The standard view on the display is the status page The current set point is displayed in the numb...

Page 73: ...level On the display the new menu level is indicated by the menu number For example moving up from menu level 4 1 5 0 causes the menu number to jump to 4 1 0 0 NOTE If the red button is pressed for tw...

Page 74: ...uld lead to material damage to the pump or system Only acknowledge errors after they have been remedied Allow faults to be remedied by qualified personnel only If in doubt consult the manufacturer For...

Page 75: ...own The symbol associated with the menu element and the setpoint or actual value are shown if applicable If the downward pointing arrow for One level down is shown press the red button to change to th...

Page 76: ...ps back to the status page Fig 32 8 6 5 Calling up information Changes cannot be made in Information menu elements These are identified on the display by the default access disable symbol To call up c...

Page 77: ...ng access disable In order to prevent impermissible changes to the pump settings all functions can be disabled When access is disabled this is shown on the status page by the default access disable sy...

Page 78: ...ations Display conditions 1 0 0 0 Setpoint Setting display of the setpoint for further information see Section 8 6 1 Adjusting the set point on page 70 2 0 0 0 Control mode Setting display of the cont...

Page 79: ...ter Number of switching on proce dures of the supply voltage each occasion the supply voltage is established after an interruption is counted 4 2 6 0 Pump kick counter Number of pump kicks that have o...

Page 80: ...us system Only displayed when BMS is active CAN field bus system Only displayed when BMS is active Gateway protocol Only displayed when BMS is active 4 4 0 0 Device data Displays device data 4 4 1 0 P...

Page 81: ...and 36 hours in 4 hour increments Displayed when internal pump cycling is activated 5 1 4 0 Pump enabled disabled Pump enabled Pump disabled 5 1 5 0 SSM Individual fault signal Only displayed in DP MA...

Page 82: ...cl all sub menus 5 5 1 0 P parameter Setting of the proportional term of the control 5 5 2 0 I parameter Setting of the integral term of the control 5 5 3 0 D parameter Setting of the derivative term...

Page 83: ...s to factory settings Caution All manual settings will be lost Not displayed when access disable is active 6 0 0 0 Error acknowl edgement For additional information see Section 11 3 Acknowledging erro...

Page 84: ...luid Depending on the temperature of the fluid and the system pres sure when the vent screw is opened completely extremely hot or extremely cold fluid in liquid or vapour form may escape or shoot out...

Page 85: ...ure side of the double pump system in the respective collector pipe The other pump will then display the status SL slave All further pump settings must now be made via the master only NOTE The procedu...

Page 86: ...controller output The sign of the P term deter mines the controller s direction of action The I or integral term of the controller provides integral control based on the system deviation A constant d...

Page 87: ...ed but the pump is only running at minimum or maximum speed without responding to changes in the parameter values 10 Maintenance Safety Maintenance and repair may only be carried out by qualified per...

Page 88: ...Maintenance work DANGER Risk of fatal injury Falling pumps or pump parts may result in life threatening injuries When performing installation work protect the pump components against falling 10 2 1 Re...

Page 89: ...3 Insert the motor with impeller and shaft seal into the pump housing and fasten using the flange screws Fig 5 Item 4 Install the pressure measuring lines of the differential pressure sensor Connect t...

Page 90: ...A Permanent error 6 B Permanent error on the 6th occurrence 5 C Warning after 5 min transition to an error permanent error on the 6th occurrence 4 D Like error type A but error type A has a higher pri...

Page 91: ...23 Short circuit earth leakage Motor or module defec tive Contact customer service A A E025 Faulty contact Module has no contact to motor Contact customer service A A Winding interrupted Motor defecti...

Page 92: ...the error within the last 24 hours and is reset after manual acknowledgement 24 hour continuous mains On or a new mains On E072 Power section fre quency converter Internal electronics error Contact cu...

Page 93: ...onds for error types A and D Press the red button again The error is acknowledged and the status page is displayed Fig 40 Error type A flowchart 1 2 3 4 Program step query Contents 1 Error code is dis...

Page 94: ...us page will be displayed NOTE The auto reset time can be set on menu number 5 6 3 0 time input 10 to 300 s Incidence X Y If the current incidenceof the erroris equaltothe maximumincidence Fig 45 Wait...

Page 95: ...l be counted up by one NOTE The error will be acknowledged automatically if the cause of the error is eliminated Wait until the remaining time is up If the current incidence x is the same as the maxim...

Page 96: ...flowchart 1 2 4 5 3 6 7 9b 9a 8 Program step query Contents 1 Error code is displayed Pump goes into emergency operation 2 Error meter is incremented 3 Error matrix AC or HV 4 SSM is activated 5 Error...

Page 97: ...ble below Information to be provided when ordering spare parts Spare part number Name description of the spare part All data on the pump and motor name plate Spare parts table See Figs 5 for a labelle...

Page 98: ...escription du produit 100 6 2 Types de r gulation 101 6 3 Fonction pompe double 102 6 4 Autres fonctions 105 7 Montage et raccordement lectrique 107 7 1 Installation 107 7 2 Raccordement lectrique 109...

Page 99: ...s notre approbation cette d claration perdra sa validit 2 S curit Ce manuel renferme des consignes essentielles qui doivent tre res pect es lors du montage et de l utilisation Ainsi il est indispensab...

Page 100: ...ou les connaissances n cessaires sauf si elles sont surveill es par une personne responsable de leur s curit ou si cette personne leur a appris comment utiliser l appareil Les enfants doivent tre sur...

Page 101: ...eut entra ner des blessures corpo relles Le transport de la pompe doit tre effectu l aide de dispositifs de suspension de charge homologu s Ils doivent tre lingu s au niveau des brides de la pompe et...

Page 102: ...xt rieur est interdite ATTENTION Risque de dommages mat riels L utilisation de substances non autoris es dans le fluide risque de d truire la pompe Les mati res solides abrasives p ex le sable accentu...

Page 103: ...de passage n est pas donn e pour tous les types de pompes REMARQUE Observer en tout cas la fiche de s curit du fluide transporter Pompe IP E DP E Notice de montage et de mise en service Propri t Valeu...

Page 104: ...s brides c t aspiration et c t refoulement se situent sur une ligne m diane Tous les corps de pompe sont dot s de pieds de pompe Le montage sur un socle de fondation est recommand Module lectronique L...

Page 105: ...vitesse constante entre nmin et nmax fig 12 Le mode de fonctionnement mode r glage d sactive tous les autres types de r gulation PID Control Lorsque les types de r gulation standard mentionn s ci des...

Page 106: ...ression diff rentielle sur cette pompe Les points de mesure du capteur de pression diff rentielle de la pompe ma tre doivent se trouver dans le tuyau collecteur concern c t aspiration et refoulement d...

Page 107: ...omparer au chapitre 6 4 Autres fonctions la page 105 6 3 2 Comportement en mode pompe double Permutation des pompes En mode pompe double une permutation des pompes est op r e toutes les 24 h r glable...

Page 108: ...interruption de la communication les deux afficheurs affi chent le code d erreur E052 Pendant la dur e de l interruption les deux pompes se comportent comme des pompes simples Les deux modules signal...

Page 109: ...i pendant l interruption de communication au niveau de l ancien ma tre le fonctionnement est interrompu par coupure r seau marche r seau l ancien ma tre d marre avec les derni res consignes qu il conn...

Page 110: ...teur de pression diff rentielle WILO fourni Valeurs de r glage entr e In1 0 10 volts correction de valeur de pression ON En cas d utilisation du capteur de pression diff rentielle Wilo ces r glages do...

Page 111: ...tion incorrecte Seul du personnel sp cialis est habilit installer la pompe AVERTISSEMENT Endommagement de la pompe par surchauffe la pompe ne doit pas tourner plus d une minute sans passage L accumula...

Page 112: ...de direction rep r e sur la bride du corps de la pompe La vanne de purge fig 17 pos 1 doit toujours tre orient e vers le haut Toute position de montage except Moteur vers le bas est autori s e Le mod...

Page 113: ...s de c ble utilis es et la protection par fusible il faut savoir qu en mode multipompes un fonctionnement bref et simultan de toutes les pompes peut survenir Pr paration Remarques Le raccordement lect...

Page 114: ...cation FI Courant de d clenchement 30 mA V rifier la nature du courant et la tension de l alimentation r seau Observer les donn es de la plaque signal tique de la pompe La nature du courant et la tens...

Page 115: ...externe des pompes Param trable au menu Service 5 1 3 2 La borne AUX r agit la pr sence d une impulsion Le pon tage unique des deux bornes permet d effectuer la permuta tion externe des pompes dans la...

Page 116: ...menu et de modifier des valeurs La pression sur le bouton rouge permet d activer un point de menu s lectionn et de confirmer des valeurs Interrupteur DIP Les interrupteurs DIP fig 9 pos 6 fig 22 se tr...

Page 117: ...t de menu pr sentant des informations sur l tat ou des r glages de l appareil non modifiables S lection R glage un point de menu permettant d acc der un r glage modifiable l ment au num ro de menu X X...

Page 118: ...se trou ver sous tension Observer les consignes g n rales de s curit 8 5 1 Page d tat de l afficheur La page d tat est la page affich e par d faut sur l afficheur La valeur de consigne actuellement d...

Page 119: ...Le nouveau niveau de menu est identifi sur l afficheur par le num ro de menu p ex en cas de retour depuis le niveau de menu 4 1 5 0 le num ro de menu passe 4 1 0 0 REMARQUE En cas de pression de 2 se...

Page 120: ...d fauts r p t s et des dommages mat riels sur la pompe ou l installation N acquitter les d fauts qu une fois leur cause limin e Seuls les techniciens sp cialis s sont habilit s liminer les d fauts En...

Page 121: ...ndant au point de menu et le cas ch ant la valeur de consigne ou la valeur r elle s affiche Si la fl che vers le bas pour un niveau plus bas s affiche appuyer sur le bouton rouge pour passer au niveau...

Page 122: ...l affichage revient la page d tat fig 32 8 6 5 Appeler des informations Les points de menu de type Information n autorisent aucune modification Ils sont repr sent s sur l afficheur par le symbole stan...

Page 123: ...p cher toute modification non autoris e des r glages de la pompe ilestpossibled activer unverrouillagedetouteslesfonctions Un verrouillage d acc s actif s affiche sur la page d tat sous la forme du sy...

Page 124: ...Symbole Valeurs Explications Conditions d affichage 1 0 0 0 Valeur de consigne R glage affichage de la valeur de consigne pour de plus amples informa tions voir chapitre 8 6 1 Adaptation de la valeur...

Page 125: ...au kick de pompe Tempsrestantjusqu auprochain kick de pompe apr s 24 h d arr t d une pompe p ex via Ext Off la pompe se met auto matiquement en marche pen dant 5 secondes 4 2 5 0 Compteur r seau acti...

Page 126: ...e SBM Message d attente SBM Message r seau activ 4 3 4 0 Ext off Signal activ de l entr e Ext off OPEN La pompe est d sactiv e SHUT La pompe est lib r e pour le fonctionnement 4 3 5 0 Type de rapport...

Page 127: ...Ma tre au mode Esclave Ne s affiche qu en mode DP MA 5 1 3 0 Permutation des pompes Ne s affiche qu en mode DP MA 5 1 3 1 Permutation manuelle des pompes proc de la permutation des pompes sans tenir c...

Page 128: ...elatifs l entr e externe des valeurs de consigne 2 5 4 1 0 In2 active non active ON Entr e externe des valeurs de consigne 2 active OFF Entr e externe des valeurs de consigne 2 non active 5 4 2 0 In2...

Page 129: ...lage par d faut les r glages par d faut ne sont pas modifi s lors de la confirma tion Ne s affiche pas en cas de verrouillage d acc s activ ON Les r glages d usine sont res taur s lors de la confirmat...

Page 130: ...s pression En fonction de la temp rature du fluide v hicul et de la pression syst me en cas d ouverture int grale de la vis de purge du fluide v hicul tr s chaud ou tr s froid peut s chapper sous form...

Page 131: ...e pompe affiche automatiquement l tat SL esclave A partir de maintenant tous les autres r glages de la pompe ne peu vent s effectuer que via le ma tre REMARQUE Apr s coup la proc dure peut tre lanc e...

Page 132: ...du r gulateur Le signe pr c dant la fraction P d termine le sens d action du r gula teur La fraction I ou galement la fraction int grale du r gulateur forme une int grale via l cart de r gulation Un c...

Page 133: ...tion PID la pompe tourne unique ment une vitesse de rotation minimale ou maximale et ne r agit pas aux modifications des valeurs de param tre le sens d action de r gu lation doit tre v rifi 10 Entreti...

Page 134: ...ute de la pompe ou de composants individuels peut entra ner des blessures mortelles Bloquer les composants de pompe pour viter leur chute lors des travaux d installation 10 2 1 Remplacer la garniture...

Page 135: ...ue et la garniture tanche dans le corps de pompe et les fixer avec les crous bride fig 5 pos 4 Monter les conduites de mesure de pression du capteur de pression diff rentielle Brancher la ligne de rac...

Page 136: ...as de d faut d faut d finitif 5 C Avertissement au bout de 5 min passage un d faut au 6e cas de d faut d faut d finitif 4 D comme type de d faut A le type de d faut A tant de priorit plus importante q...

Page 137: ...rifier corriger le point de fonctionnement B A D p ts dans la pompe Appeler le service apr s vente E023 Court circuit court circuit la terre Moteur ou module d fec tueux Appeler le service apr s vent...

Page 138: ...de nouveau R seau activ D fauts de l lectro nique E070 erreur de communica tion interne SPI Erreur d lectronique interne Appeler le service apr s vente A A E071 D faut EEPROM Erreur d lectronique int...

Page 139: ...secondes Appuyer de nouveau sur le bouton rouge Le d faut est acquitt et la page d tat s affiche Fig 40 Type de d faut A sch ma 1 2 3 4 Demande d tape de programme Contenu 1 Le code d erreur s affich...

Page 140: ...acquitt et la page d tat s affiche REMARQUE Le d lai de r initialisation automatique peut se r gler au menu num ro 5 6 3 0 consigne de temps de 10 300 s Occurrence X Y Si l occurrence actuelle du d fa...

Page 141: ...ndes l occurrence actuelle est augment e de un REMARQUE L limination de la cause du d faut acquitte automatiquement le d faut Patienter le temps restant Si l occurrence actuelle x est gale l occurrenc...

Page 142: ...2 4 5 3 6 7 9b 9a 8 Demande d tape de programme Contenu 1 Le code d erreur s affiche La pompe passe en r gime de secours 2 Le compteur de d fauts augmente 3 Matrice de d faut AC ou HV 4 SSM est activ...

Page 143: ...ication des diff rents compo sants Indications indispensables pour les commandes de pi ces de rechange Num ros de pi ces de rechange D signations de pi ces de rechange Ensemble des donn es de la plaqu...

Page 144: ...ving en werking 146 6 1 Productomschrijving 146 6 2 Regelingstypen 147 6 3 Dubbelpompfunctie 148 6 4 Overige functies 151 7 Installatie en elektrische aansluiting 153 7 1 Installatie 153 7 2 Elektrisc...

Page 145: ...erlegd wordt deze verklaring ongeldig 2 Veiligheid Deze gebruikshandleiding bevat basisrichtlijnen die bij de montage en bij de bediening dienen te worden nageleefd De gebruikshandleiding dientdan ook...

Page 146: ...en gebrek aan ervaring en of kennis behalve als zij onder toezicht staan van een voor hun veiligheid verantwoordelijke persoon of van deze persoon instructies hebben gekregen over het gebruik van het...

Page 147: ...skundig transport kan persoonlijk letsel veroorzaken De pomp dient met goedgekeurde hijswerktuigen te worden getransporteerd Deze moeten aan de pompflenzen en indien nodig aan de buitenkant van de mot...

Page 148: ...uit deze serie buiten op te stellen VOORZICHTIG Gevaar voor materi le schade Niet toegestane stoffen in de vloeistof kunnen de pomp vernielen Door abrasieve vaste stoffen bijv zand neemt de slijtage v...

Page 149: ...s aan Niet bij alle pomptypen wordt een doorstroomwaarde uitgegeven AANWIJZING Het veiligheidsinformatieblad van de te pompen vloeistof moet in ieder geval in acht worden genomen Pomp IP E DP E Inbouw...

Page 150: ...erd d w z de flenzen aan de zuig en perszijde liggen op een middellijn Alle pomphuizen zijn voorzien van pompvoeten Het wordt aanbevolen om voor de montage een funderingssokkel te gebruiken Elektronic...

Page 151: ...g 12 De bedrijfssituatie Regelbedrijf deactiveert alle overige regelingstypen PID controle Indien de hierboven genoemde standaard regelingstypen niet toege past kunnen worden bijv bij een Y buisinstal...

Page 152: ...in stroomrichting de linkerpomp Op deze pomp moet de verschildruksensor worden aangesloten Demeetpuntenvandeverschildruksensorvandehoofdpompmoeten in de desbetreffende verzamelbuis op de zuig en drukz...

Page 153: ...erige functies op pagina 151 6 3 2 Gedrag in dubbelpompbedrijf Pompwisseling In het dubbelpompbedrijf vindt er om de 24 uur instelbaar een pompwisseling plaats De pompwisseling kan intern tijdgestuurd...

Page 154: ...an de communicatie Bij een onderbreking van de communicatie geven beide displays de foutcode E052 weer Gedurende de onderbreking gedragen beide pompen zich als afzonderlijke pompen Beide modules melde...

Page 155: ...Netvoeding uit en inschakelen Wanneer tijdens de onderbreking in de communicatie op de voorma lige master het bedrijf door het in en uitschakelen van de netvoe ding wordt verlaten start de voormalige...

Page 156: ...ingen zijn geconfigu reerd voor de meegeleverde WILO verschildruksensor Instelwaarden ingang In1 0 10 volt drukwaardecorrectie ON Indien de meegeleverde Wilo verschildruksensor wordt gebruikt dienen d...

Page 157: ...deskundige hantering Pomp uitsluitend door vakpersoneel laten installeren VOORZICHTIG Beschadiging van de pomp door oververhitting De pomp mag niet langer dan n minuut zonder doorstroming draaien Door...

Page 158: ...door de pomp wordt gedragen De stroomrichting moet overeenkomen met de pijl op de flens van het pomphuis Het ontluchtingsventiel fig 17 pos 1 moet altijd naar boven wijzen Elke inbouwpositie behalve...

Page 159: ...t meerpompenbedrijf mogelijk is dat alle pompen kortstondig gelijk tijdig in bedrijf zijn Voorbereiding aanwijzingen De elektrische aansluiting moet via een vast gelegde netaansluitlei ding plaatsvind...

Page 160: ...omgevoelige uitvoering van het type B zijn toegestaan Aanduiding FI Afschakelstroom 30 mA Stroomsoort en spanning van de netaansluiting controleren Gegevens op het typeplaatje van de pomp in acht neme...

Page 161: ...pompwisseling Parametreerbaar in servicemenu 5 1 3 2 De klem AUX reageert op een optredende impuls Door een malig overbruggen van de beide klemmen wordt een externe pompwisseling uitgevoerd indien ge...

Page 162: ...ijzigen Door de rode knop in te drukken kunt u een geselecteerd menu element activeren of waarden bevestigen DIP schakelaars De DIP schakelaars fig 9 pos 6 fig 22 bevinden zich onder de afdekking van...

Page 163: ...nformatie een menu element dat informatie weergeeft over de apparaatstatus of instellingen die niet kunnen worden gewijzigd Selectie instelling een menu element dat toegang biedt tot een veranderbare...

Page 164: ...r nog spanning aanwezig zijn Algemene veiligheidsaanwijzingen in acht nemen 8 5 1 Statuspagina van weergave De standaardweergave op het display is de statuspagina Het actueel ingestelde setpoint wordt...

Page 165: ...dt op het display aangege venmethetmenunummer Bijvoorbeeld hetmenunummerspringtbij het terugkeren van menuniveau 4 1 5 0 naar 4 1 0 0 AANWIJZING Als de rode knop twee seconden wordt ingedrukt terwijl...

Page 166: ...ngen en materi le schade aan de pomp of installatie leiden Fouten pas bevestigen nadat de oorzaak is verholpen Storingen alleen door vakpersoneel laten verhelpen Bij twijfel contact opnemen met de fab...

Page 167: ...at bij het menu element hoort en het setpoint of de actuele waarde wor den evt weergegeven Als de naar beneden wijzende pijl Niveau lager wordt weergegeven de rode knop indrukken om naar het volgende...

Page 168: ...naar de statuspagina fig 32 8 6 5 Informatie oproepen Bij menu elementen van het type Informatie kunnen geen wijzigin gen worden aangebracht Deze worden gekenmerkt door het stan daardsymbool Toegangsb...

Page 169: ...gingen in de instellingen van de pomp te voorkomen kan voor alle functies een blokkering worden geacti veerd Een actieve toegangsblokkering wordt op de statuspagina weergege ven door het standaardsymb...

Page 170: ...pe Symbool Waarden toelichtingen Weergavevoorwaarden 1 0 0 0 Setpoint Instelling weergave van het set point voor meer informatie zie hoofdstuk 8 6 1 Aanpassen van het setpoint op pagina 162 2 0 0 0 Re...

Page 171: ...tisch 4 2 5 0 Teller netvoeding aan Aantal inschakelingen van de voedingsspanning elke herin schakeling van de voedings spanning na een onderbreking wordt geteld 4 2 6 0 Teller pomp kicks Aantal uitge...

Page 172: ...ief is LON Veldbussysteem Wordt alleen weergegeven als BMS actief is CAN Veldbussysteem Wordt alleen weergegeven als BMS actief is Gateway Protocol Wordt alleen weergegeven als BMS actief is 4 4 0 0 A...

Page 173: ...Wordt alleen bij DP MA weergegeven Externe pompwisseling Wordt alleen bij DP MA weergegeven zie klem AUX 5 1 3 3 Intern tijdinterval Instelbaar tussen 8 en 36 uur in stappen van 4 uur Wordt weergegev...

Page 174: ...OFF Externe setpoint ingang 2 inactief 5 4 2 0 In2 instelbereik Instelling instelbereik Mogelijke waarden 0 10 V 2 10 V 0 20 mA 4 20 mA Wordt niet weergegeven als In2 inactief 5 5 0 0 PID parameter In...

Page 175: ...et bevestigen niet gewijzigd Wordt bij actieve toegangs blokkering niet weergege ven ON Instellingen worden bij het bevestigen naar de fabrieks instelling gereset Voorzichtig Alle handmatig ingestelde...

Page 176: ...de temperatuur van het te pompen materiaal en de systeemdruk kan bij het volledig openen van de ontluchtings schroef heet materiaal in vloeibare of gasvormige toestand vrijko men of onder hoge druk na...

Page 177: ...status SL slave weer Alle overige instellingen van de pomp kunnen vanaf nu enkel nog via de master worden ingesteld AANWIJZING De procedure kan later handmatig gestart worden door het menu 5 1 2 0 te...

Page 178: ...actuele en de setpointwaarde op de uitgang van de regelaar Het teken v r het P aandeel bepaalt de werking van de regelaar Het I aandeel ofwel het integrale aandeel van de regelaar integreert via de re...

Page 179: ...maximaal toerental draait en niet op veranderingen van de parameter waarden reageert moet de werking van de regelaar worden gecontro leerd 10 Onderhoud Veiligheid Onderhouds en reparatiewerkzaamheden...

Page 180: ...rden gekoeld 10 2 Onderhoudswerkzaamheden GEVAAR Levensgevaar Door het eraf vallen van de pomp of afzonderlijke onderdelen kun nen mensen levensgevaarlijk letsel oplopen Onderdelen van de pomp bij ins...

Page 181: ...chting in het pomphuis plaatsen en met de flensschroeven fig 5 pos 4 bevestigen Drukmeetleidingen van de verschildruksensor monteren Netaansluitleiding vastklemmen Afsluitarmaturen voor en achter de p...

Page 182: ...1 Mechanische storingen Fouttype Toelichting Prioriteit A Definitieve fout 6 B Bij 6 keer definitieve fout 5 C Waarschuwing na 5 min overgang naar een fout Bij 6 keer definitieve fout 4 D Zoals A all...

Page 183: ...rtemperatuur verlagen E021 Overbelasting motor Bedrijfspunt ligt buiten de karakteristiek Bedrijfspunt controleren corri geren B A Afzettingen in de pomp Contact opnemen met servicedienst E023 Kort aa...

Page 184: ...llende pompen Contact opnemen met ser vicedienst F F E052 DP MP communica tie timeout Kabel MP communicatie defect Kabel en kabelverbindingen controleren E E Elektronica fout E070 Interne communica ti...

Page 185: ...ltijd 60 seconden Rode knop opnieuw indrukken De fout is bevestigd en de statuspagina wordt weergegeven Fig 40 Fouttype A schema 1 2 3 4 Programma stap opvraag Inhoud 1 Foutcode wordt weergegeven Moto...

Page 186: ...tuspagina weergegeven AANWIJZING De autoresettijd kan onder het menunummer 5 6 3 0 worden inge steld tijdsinstelling 10 tot 300 s Optreden X Y Indien het actuele optreden van de fout gelijk is aan het...

Page 187: ...het actuele optreden met de waarde n verhoogd AANWIJZING Door de oorzaak van de fout te verhelpen wordt de fout automatisch bevestigd Wachten tot de resterende tijd verstreken is Indien het actuele o...

Page 188: ...ttype E schema 1 2 4 5 3 6 7 9b 9a 8 Programma stap opvraag Inhoud 1 Foutcode wordt weergegeven Pomp schakelt om naar het noodbedrijf 2 Foutteller wordt verhoogd 3 Foutenmatrix AC of HV 4 SSM wordt ge...

Page 189: ...ruiken In de onderstaande tabel kunnen afzonderlijke onderdelen worden ge dentificeerd Vereiste gegevens bij de bestelling van reserveonderdelen Nummers reserveonderdelen Aanduidingen reserveonderdele...

Page 190: ......

Page 191: ......

Page 192: ......

Page 193: ...95 EC are realized according annex I No 1 5 1 of the EC Machinery directive 2006 42 EC Les objectifs protection de la directive basse tension 2006 95 CE sont respect es conform ment appendice I n o 1...

Page 194: ...zym deklarujemy z pe n odpowiedzialno ci e dostarczony wyr b jest zgodny z nast puj cymi dokumentami Sm rnice ES pro strojn za zen 2006 42 ES dyrektyw maszynow WE 2006 42 WE EC 2006 42 EG C le t kaj c...

Page 195: ...ather and Platt Pumps Ltd Pune 411019 T 91 20 27442100 service pun matherplatt co in Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 citrawilo cbn net id Ireland WILO Engineering...

Page 196: ...dustrie WILO SE Nortkirchenstra e 100 44263 Dortmund T 0231 4102 7900 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 kundendienst wilo com Erreichbar Mo So von 7 18 Uhr In Notf llen t glich auch von...

Reviews: