106
Coding in the delivered condition
Possible change
A4:0
With frost protection
A4:1
No frost protection; this setting is on-
ly possible if code "A3:
–
9" has been
set.
!
Please note
"Important": Observe for cod-
ing address "A3".
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump "OFF" when the
outside temperature (OT) is 1 K
higher than the set room tempera-
ture (RT
set
)
OT
>
RT
set
+ 1 K
A5:0
Without heating circuit pump logic
function
A5:1
to
A5:15
With heating circuit pump logic func-
tion: heating circuit pump "OFF"; see
following table
Parameter address A5:...
With heating circuit pump logic function: Heating circuit pump "OFF"
1
OT
>
RT
set
+ 5 K
2
OT
>
RT
set
+ 4 K
3
OT
>
RT
set
+ 3 K
4
OT
>
RT
set
+ 2 K
5
OT
>
RT
set
+ 1 K
6
OT
>
RT
set
7
to
OT
>
RT
set
–
1 K
15
OT
>
RT
set
–
9 K
Coding in the delivered condition
Possible change
A6:36
Extended economy mode
disa-
bled
A6:5
to
A6:35
Extended economy mode enabled:
The burner and heating circuit pump
will stop at a variable value, adjusta-
ble between 5 and 35 °C plus 1 °C.
Mixer is being closed. Basis for this
is the adjusted outside temperature.
This is composed of the actual out-
side temperature and a time con-
stant that takes account of the way
an average building cools down.
A7:0
Only for heating circuit with mixer:
Without mixer economy function
A7:1
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
■
If the mixer has been trying to
close for longer than 20 min.
Heating circuit pump "ON":
■
If the mixer changes to control
function
■
If there is a risk of frost
A8:1
Heating circuit with mixer creates a
demand on internal circulation
pump.
A8:0
Heating circuit with mixer does not
create a demand on internal circula-
tion pump.
Codes
Coding level 2
(cont.)
5775 636 GB
Codes
Summary of Contents for C3TB
Page 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Page 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Page 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Page 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Page 187: ...187 5775 636 GB ...