180
Settings and test values
Set value
Commissioning Maintenance/
service
Date
Signature
Type of fuel cell
FC-V75CF1HD
FC-V75FS1AD
Tick type.
Static pressure
mbar
kPa
≤
57.5
≤
5.75
Supply pressure (flow pressure)
for natural gas E
for natural gas LL
mbar
kPa
17.4-25
1.74-2.5
Tick gas type.
Carbon dioxide content CO
2
For natural gas
■
At lower heating output
% by vol.
7.5-9.5
■
At upper heating output
% by vol.
7.5-9.5
Oxygen content O
2
■
At lower heating output
% by vol.
4.0-7.6
■
At upper heating output
% by vol.
4.0-7.6
Carbon monoxide content CO
■
At lower heating output
ppm
< 1000
■
At upper heating output
ppm
< 1000
Fuel cell module
■
Electrical output
W
750
■
Power generated
kWh
■
Amount of gas consumed
m
3
■
Hours run
h
■
Distilled water filter replaced
■
Air filter replaced
Commissioning/service reports
Commissioning/service reports
5775 636 GB
Appendix